Qmark Environmental Hot Water / Steam Heated Air Curtains User Manual

Environmental series air curtains, Specifications and performance, Description

Advertising
background image

Specifications and Performance

INSTALLATION & OPERATING INSTRUCTIONS & PARTS MANUAL

FOR ALL 120 and 230 VOLT

1/4, 1/2 AND 3/4 H.P. MOTOR MODELS

READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, OR MAINTAIN THE
PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION.
FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY
DAMAGE! RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.

REFER TO INDIVIDUAL MODEL NUMBERS

FOR UNIT WIDTH

11

7

/

8

3

1

/

4

15

3

/

4

12

1

/

2

Description

Leading Edge air curtains produce a wall of continuously
flowing air that acts as a thermal barrier against outside
air and flying insects. These air curtains maintain interior
conditioned temperature and prevent heated or cooled
air from escaping through open doorways. They reduce
humidity and loss of cold air when used over freezer and
cooler doors. High traffic area doors can be left open,
eliminating wear and nuisance of opening and closing
automatic and manual doors. Used over service
entrances, receiving doors, customer entrances, access
doors, etc. ... air curtains provide protection against
insects, dust, odor, fumes and other contaminant’s.

Dimensions - See Fig. 1

Note that all dimensions (except width) are the same on
all environmental series units. Model number indicates
width of unit.
(Example: E4800 indicates a 48” wide unit.)

Unpacking

NOTE

-

AFTER

UNPACKING

UNIT,

INSPECT

CAREFULLY FOR ANY DAMAGE THAT MAY HAVE
OCCURRED DURING TRANSIT. CHECK FOR LOOSE,
MISSING OR DAMAGED PARTS.

1. With packaged unit on the floor, carton arrows should

point upward.

2. Carefully remove staples from top of carton and fold

back sides.

3. Carefully remove cabinet from carton by lifting out unit

using straps provided.

HP

MAX.

RPM

MAX.

MOTOR

WATTS

120V, 60HZ

MAX.

AMPS

230V, 60HZ

MAX.

AMPS

MAX.

FT. PER MIN.

AT NOZZLE

36”

38”

42”

48”

60”*

††

AVG. CFM AT NOZZLE FOR MOTOR SHOWN

IN VARIOUS CABINET SIZES

1/4

1/2

3/4

1100

1745

1700

125

480

750

3.4

5.2

7.8

.7

2.2

2.6

2500

3800

4850

1620

2460

3140

1670

2535

3240

2000

3040

3880

1795

2730

3480

2880

††

4375

††

4580

Environmental

Series

Air Curtains

††

Two motor unit.

Fig. 1

Advertising
This manual is related to the following products: