Qmark Environmental Electric Heated User Manual

Installation & maintenance instructions, Environmental series, Read and save these instructions

Advertising
background image

1

ENVIRONMENTAL SERIES

ELECTRICALLY HEATED AIR CURTAINS

8 KW THROUGH 48 KW

36” THROUGH 144”

Read Carefully -

These instructions are written to help you

prevent difficulties that might arise during installation of the

unit. Studying the instructions first may save you consider-

able time and money later. Observe the following proce-

dures, and cut your installation time to a minimum.
CAUTION - TO REDUCE RISK OF FIRE AND ELECTRIC

SHOCK OBSERVE THE FOLLOWING:

1. Disconnect all power coming to the unit at main service panel

before wiring or servicing. Lock service panel to prevent power

from being switched on accidentally.

NOTE: Do not depend upon a thermostat or other switch as the sole

means of disconnecting power when installing or servicing the unit.

Always disconnect power at the main service panel as described

above.

2. All wiring should be done by a qualified electrician, using copper

wire only and in accordance with the National Electrical Code

(NEC), all applicable code and ordinances, including fire rated

construction, and all sections of this manual. Any variance voids

the warranty and may create unsafe conditions.

3. To prevent the risk of electric shock, the unit must be properly

grounded. This should be accomplished by connecting a bond-

ing conductor between the disconnecting means and the

grounding lug provided in the Main Control Box of the unit. Each

cabinet wiring compartment is provided with grounding lugs for

connecting bonding conductors between each cabinet and the

Main Control Box. To ensure a proper ground, the grounding

means must be tested by a qualified electrician.

4. Verify the power supply voltage coming to unit matches the rat-

ings printed on the heater nameplate before energizing.

5. This unit can be hot when in use. To avoid burns, do not let bare

skin touch hot surfaces.

6. Do not insert or allow foreign objects to enter any ventilation or

exhaust opening as this may cause an electric shock, fire or

damage to the unit.

7. Do not block air intakes or exhaust in any manner. Keep com-

bustible materials, such as crates, drapes, etc., away from air

curtain.

8. This unit has hot and arcing or sparking parts inside. Do not use

it in areas where gasoline, paint or flammable liquids are used

or stored.

9. Use this unit only as described in this manual. Any other use

not recommended by the manufacturer may cause fire, electric

shock, or injury to persons. If you have questions contact the

manufacturer.

10. This unit is not approved for use in corrosive atmospheres such

as marine, green house or chemical storage areas.

READ AND SAVE THESE INSTRUCTIONS

WARNING

!

Dear Owner,
Congratulations! Thank you for purchasing this new air curtain manufactured by Marley Engineered Products. You have made

a wise investment selecting the highest quality product in the industry. Please carefully read the installation and

maintenance instructions shown in this manual. You should enjoy years of efficient service with this product from Marley

Engineered Products... the industry’s leader in design, manufacturing, quality and service.

... The Employees of Marley Engineered Products

Installation & Maintenance Instructions

®

15 3/4”

13”

Refer to individual model numbers

for unit width

8 1/4”

4 7/8”

11 7/8”

Advertising