Tjernlund SS1C SideShot with UC1 Universal Control (Version X.02) 8504103 Rev 07/02 User Manual

Page 3

Advertising
background image

2

SPECIFICATIONS

Motor: 115/1/60, 3300 RPM, 212 watts, 2.28 FLA
Fan Proving Switch: Non-adjustable, N/O with a set point of -.04" W.C.

High Limit: Manual reset, N/C contacts, open at 79oC (175oF) + 8oC (15oF)
UC1 Universal Control: See UC1 Universal Control Board Features on page 4.
Pre-Purge: Options (0, 15, 30, 60 seconds); Post-Purge: Factory set at 2 minutes, Options (0, 30 seconds or 1, 2, 4, 8, 16 minutes).

See Page 5 for Pre / Post-purge options.

GENERAL INFORMATION

These units have been factory tested and rated in accordance with the following Canadian Standards: CAN/CSA - B140.0-M87
General Requirements For Oil Burning Equipment; CAN/CSA - B139-M91 Installation Code For Oil Burning Equipment;
CAN3 - B255-M81 Mechanical Flue - Gas Exhausters.

Each SideShot is electrically factory line tested before shipment.

After opening carton, inspect thoroughly for hidden damage. Wheel should rotate freely. If any damage is found notify freight car-
rier and your distributor immediately and file a concealed damage claim.

INSTALLATION RESTRICTIONS

1. The SideShot may not be installed on condensing appliances, incinerators, incinerating toilets, or solid fuel burning appliances.

2. The SideShot Model SS1C is Listed for Oil Fired appliances only.

3. The SideShot may only be installed on appliances equipped with a barometric draft control.

4. The SideShot shall not be installed where flue gas temperatures exceed 301oC (575oF) at its inlet. Flue gas temperature

verification:

A) On oil fuel, verify flue gas temperature at SS1C inlet is at or above 250oF (121oC) after 5 minutes of operation during

setup. See “Oil Draft Adjustment Procedure” on page 17, step 10.

AND

B) Measure temperature of flue gases at the inlet to the SideShot at time of installation. Temperature should be

measured after appliance and SideShot have operated for at least 15 minutes, allowing flue gas temperature to stabilize.

5. The maximum recommended wall thickness is 39cm (15”).

6. Vent runs of over 4.5 linear meters (15 linear feet) should use an approved, insulated vent connector to prevent problems

related to sulfur condensation.

CAUTIONS

Improper installation, adjustment, alterations, service or maintenance can cause injury, property damage or death. Refer to this
manual. For assistance or additional information consult a qualified installer, service agency or the equipment supplier.

Do not exceed the recommended input range of the SideShot. Under no circumstances shall the minimum draft adjustment be
used for the larger input range of this product. Improper adjustment may result in the dispersion of flue products (carbon monox-
ide) into the building interior causing carbon monoxide poisoning or death.

If oil nozzle is changed or other equipment is added perform “Draft Adjustment Procedure” on pages 16, 17 again.

12 1/4"

16 1/2"

27 3/8"

A

B

C

15 1/8"

8"

D

13 3/4"

E

F

7 3/4"

G

14 3/4"

H

23 1/4"

I

Rough-In
8” Height
8 3/8” Width

FRONT VIEW

SIDE VIEW