A venting system shall not terminate within 1.8 m (6ft) of the following:
• A window, door or mechanical air supply inlet of any building, including soffit openings
• A gas service regulator vent outlet
• A combustion air inlet
• A property line
• A direction facing combustible materials or openings of surrounding buildings

A venting system shall not terminate within 1m (3ft) of the following:
• Above a gas meter/regulator assembly within 1m (3ft) horizontally of the vertical centreline of the regulator
• A oil tank or an oil tankfill inlet
• The inside corner of an L-shaped structure

A venting system shall not terminate within .3m (1ft) of the following:
• Above grade level or any surface that may support snow, ice, or debris

CAUTION: The owner of the SS2 must keep the area around the vent terminal free of snow, ice and debris.

INSTALLATION TOOLS REQUIRED

Nut Runner Set

Drill w/Bits

Combination Wrench Set

Screwdriver Set

Wire Cutter/Stripper

Draft Gauge

Smoke Tester

CO

2

Analyzer

Reciprocating Saw

If possible, do not terminate the SS2 on a wall that faces the direction of the prevailing
winds. Backdrafts by severe winds can cause oil odors to remain in the structure
and/or interrupt equipment operation.