General Information for Connecting Vent Pipes

Crimped End Pipes

Before joining elbows and pipes, apply a bead of high
temperature sealant to the crimped end of the elbow or
pipe.

Join the pipes using a 2” (51mm) overlap and secure
the joints with three (3) sheet metal screws. (Fig. 16)
Wipe off excess sealant.

Canadian Installations:

The venting system must be installed in accordance
with the current CSA-B149.1 installation code.

USA Installations:

The venting system must conform to local codes and/
or the current National Fuel Code ANSI Z223.1/NFPA
54.

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

A =
Combustible
6" (152 mm)

Noncombustible
2" (51 mm)

B =
Combustible
6" (152 mm)

Noncombustible
2" (51 mm)

A

Balcony
with no side wall

G =
Combustible
Noncombustible
12" (305 mm)

G

Balcony
with perpendicular side wall

H = 24" (610 mm)

J = 20" (508 mm)

H

J

B

Recessed Location

C = Maximum depth of 48"
(1219mm) for recessed
location.

D = Minimum width for back wall
of a recessed location.
Combustible 38" (965 mm)
Noncombustible 24" (610 mm)

E = Clearance from corner in
recessed location.
Combustible 6" (152 mm)
Noncombustible 2" (50 mm)

C

D

C

E

V

V

Combustible &
Noncombustible

V

V

V

CFM115

Fig. 15 Termination clearances.

1" (25 mm) from
crimped end of pipe

Screw
Holes

CFM175

Fig. 16 Apply a bead of high temperature sealant.

Only venting components manufactured by Vermont
Castings, Majestic Products may be used in Direct
Vent systems.