Vertical through-the-roof installation – Vermont Casting DVRT43 User Manual

Page 20

Advertising
background image

20

Vermont Castings, Majestic Products DVRT36/ 39/ 43

10002428

Up to two (2) 45

°

elbows may be used within the

horizontal run. For each 45

°

elbow used on the

horizontal plane, the maximum horizontal length
must be reduced by 18” (450mm).

Example: Maximum horizontal length

No elbows

=

10’ (3m)

1 x 45

°

elbows

=

8.5’ (2.6m)

2 x 45

°

elbows

=

7’ (2.1m)

A minimum of an 8’ (2.5m) vertical rise is required.

Two (2) sets of 45

°

elbows offsets may be used

within the vertical sections. From 0 to a maximum of
8’ (2.5m) of vent pipe can be used between elbows.
(Fig. 34)

7DVCS supports offsets. (Fig. 34) This application
requires you to first determine the roof pitch and
use the appropriate starter kit. See Venting
Components List.

The maximum angular variation allowed in the
system is 270

°

. (Fig. 34)

Minimum height of the vent above the highest point
of penetration through the roof is 2’ (610mm). (Fig.
37) See Note 2 on Page 12.

1. Locate your fireplace.

2. Plumb to center of the 4” flue collar from ceiling

above and mark position.

3. Cut opening equal to 9

¹⁄₂

” x 9

¹⁄₂

” (240 x 240mm).

4. Proceed to plumb for additional openings through

the roof. In all cases, the opening must provide a
minimum of 1” (25mm) clearance to the vent pipe;
i.e., the hole must be at least 9

¹⁄₂

” x 9

¹⁄₂

” (240 x

240mm).

5. Place fireplace into position.

6. Place firestop(s) #7DVFS or Attic Insulation Shield

#7DVAIS into position and secure. (Fig. 35)

Vertical Through-the-Roof Installation

7. Install roof support and roof flashing, making sure

the upper flange is below the shingles. (Fig. 36)

8. Install appropriate pipe sections until the venting is

above the flashing. (Fig. 38)

9. Install storm collar and seal around the pipe.

10. Add additional vent lengths for proper height.

(Fig. 37)

11. Apply high temperature sealant to 4” and 7” collars

of vertical vent termination and install.

If there is a room above ceiling level, fire
stop spacer must be installed on both
the bottom and the top side of the
ceiling joists. If an attic is above ceiling
level a 7DVAIS (Attic Insulation Shield)
must be installed.

The enlarged ends of the vent section
always face downward.

Typical Roof

Support

Application

Typical Ceiling

Support

Application

FP1184

Fig. 36 Venting supports.

1

2

3

4

1 + 2 + 3 + 4 = 270

°

FP1179

Fig. 34 Maximum elbow usage.

1

2

3

4

Attic
Insulation Shield

Upper Floor

Ceiling
Installation

Joist

Nails (4)

Firestop
Spacer

FP1029

Fig. 35 Attic insulation shield and firestop spacer.

11"

(279mm)

11"

(279mm)

Advertising
This manual is related to the following products: