Som 7 si, Dt o, Dt f – STIEBEL ELTRON SOM 7 SI User Manual

Page 23: S mx, Orec, O tc, Ah o, T1 0-t3 f, Ohqm, Hnd1

Advertising
background image

© 08042 som_7_si.monen.ind

d

23

|

SOM 7 SI

Display

Code

Parameter Name

and Reference

Recommended Setting and Explanation

(All temperatures in °F)

DT O

Switch on Temperature

Difference (p. 17)

15° Setting this too low can cause the circulator to cycle on and
off too frequently.

DT F

Switch off Temperature

Difference (p. 17)

Too high of a

ΔT between DT O and DT F can cause the

circulator to switch on and off too frequently.

S MX

Maximum Store

Temperature (p. 17)

140° This will prevent the temperature at the top of the tank
from getting hot enough to cause the T & P valve to release.
This will also allow the cooling function to operate effectively.

EM

Collector Emergency

Shutdown Temperature

(p. 18)

310° This prevents the HX fluid directly behind that in the
sensor well from causing the system to go into emergency
shutdown mode as soon as the cooling function is activated.

OCX

System Cooling
Function (p. 18)

On Failure to change this option to ‘on’ will likely result in
overheating of the system at some point.

CMX

Maximum Collector

Temperature (p. 18)

230° Having a relatively large

ΔT between CMX and EM

prevents the HX fluid directly behind that in the sensor well
from causing the system to go into emergency shutdown mode
as soon as the cooling function is activated.

OCN

Minimum Collector

Temperature (p. 18)

Off The

ΔT between DT O and DT F achieves the requisite

effect for most situations.

OCF

Antifreeze Option

(p. 18)

Off Unless the system is located in a region which rarely
experiences temperatures near freezing, and a very low glycol
to water percentage is being used.

OREC

Recooling Function

(p. 19)

On This prevents a cumulative overheating of the system by
ensuring a relatively high

Δt between the tank temperature and

and the security switch-off of the tank (205°).

O TC

Tube Collector

Function (p. 19)

Off Unless the system is utilizing tube collectors.

AH O

Thermostat Switch-On

Temperature (p. 20)

115 Or whatever temperature the user wants the boiler to
begin heating the tank water via the upper heat exchanger.

AH O

Thermostat Switch-Off

Temperature (p. 20)

125 Or whatever temperature the user wants the boiler to
stop heating the tank water via the upper heat exchanger.

t1 0-t3 F

Thermostat Switching

Times (p. 20)

00:00 Unless there are certain times in the day when the boiler
loop should not switch on.

OHQM

Energy Production

Measurement (p. 16)

Off Unless the installer has installed a sensor in position S4 and
wishes to utilize this function.

HND1

Solar Pump Operating

Mode (p. 20)

Auto This is the normal operating mode. The other two
modes are for testing, charging, etc.

HND2

Boiler Loop Operating

Mode (p. 20)

Auto This is the normal operating mode. The other two
modes are for testing, charging, etc.

LANG

Language (p. 20)

En (English) For most applications in North America this is
appropriate, with some exceptions.

4.2.2 Recommended Settings for Standard DHW System with Boiler Backup (Arr. 3)