Som 7 si, Unit – STIEBEL ELTRON SOM 7 SI User Manual

Page 24

Advertising
background image

SOM 7 SI

© 08042 som_7_si.monen.ind

d

|

24

Display

Code

Parameter Name

and Reference

Recommended Setting and Explanation

(All temperatures in °F)

UNIT

Units for Temperature

Display (p. 20)

FAH For most applications in North America this is
appropriate, but it is purely a matter of preference.

Please note that advanced users may desire to adjust certain parameters differently depending

on the circumstances. These suggested settings are merely a manner in which to configure the

unit that will avoid damage to the system from overheating. Installing the SOM 7 with the default

settings will likely result in an overheating condition of the solar system.

R

W

Tac o

S R 501

(T ypic al Wiring)

N

H

6

N/O

5

B oiler C ontrol

B oard

Thermostat

Input

S OM 7

15

16

4.2.2.1 SOM 7 Wiring Diagram for Connection to Cold Start Boiler

In order to interface the SOM 7 with the boiler control board of a typical boiler (which does

not heat up the boiler water unless a zone calls for heat) it is necessary to incorporate a

relay circuit. Below is a wiring diagram in which a commonly used single zone controller in

conjunction with a SOM 7 is controlling such a boiler.