Network Coordinator Installation and Configuration

6.24.13 06325C © Inovonics, 2013 - www.inovonics.com

16

3.1.1 Configure the Network Coordinator

Note:

This procedure is typically performed at Inovonics before shipping.

To configure the network coordinator:

1

Access the Radius interface and log in.

2

Click “Install Setup.”

3

Click on “Process Setup.”

4

Choose “Serial Alarm” from the “Interface Name” dropdown menu.

5

Click “Add New Interface.”

6

Enter an “Interface Name.”

• Be sure to name the interface something that you and your customer will

recognize. Any device that enters the Radius system through this process
will be given a System ID “processname_xxxxx.”

• We recommended that the process name be only one word, such as

“coordinator.”

7

Check the box for “Start Interface when Services Start.”

8

Check the box for “Automatically Create New Devices.”

• You will only want this checked during installation. Once you’ve

completed installation, return to this screen and uncheck it to ensure
devices in neighboring systems don’t impact your system.

9

Set the “Debug Level:” to “None.”

10

Select “Inovonics EchoStream” from the “Serial Interface Type.”

11

Enter a NID for the system in the “EchoStream Network ID” field. Any
number, 1-31, will work.

12

If you will be immediately registering repeaters, check the box for “Add
new Echostream repeaters to NID when Reset button pressed.”

Note:

You will only want this checked during installation. Once you’ve completed
installation, return to this screen and uncheck it to ensure devices in neighboring
systems don’t impact your system.

13

Set the “Minimum Activity Interval” to “3.”