GF-123

Benchmark 2.0LN Low NOx Boiler

Appendix A

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual Menu Items

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 121 of 170

Table A-1: Boiler Menu Item Descriptions-Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than
the proportional band setting (1 to 120°F), the fire
rate will be less than 100%. If the error is equal to
or greater than the proportional band setting, the fire
rate will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each minute
to move towards the setpoint. Gain is adjustable
from 0.00 to 1.00 (Default is 0.10).

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of
change of the setpoint error. This is the time that
this action advances the output.

Reset Defaults?

Allows Tuning Menu options to be reset to their
Factory Default values.