Appendix e: boiler default settings, Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual
Page 133

GF-123
Benchmark 2.0LN Low NOx Boiler
Appendix D
OMM-0046_0E
I
nstallation, Operation and Maintenance Manual Reset Ratio Charts
PR1 08/20/12
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288
Page 133 of 170
APPENDIX E: BOILER DEFAULT SETTINGS
Table E-1: Boiler Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
2000 MBH
Fuel Type
Natural Gas
Boiler Mode
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
195°F
Temp Hi Limit
195°F
Max Valve Position
100%