Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 59

Advertising
background image

GF-123

Benchmark 2.0LN Low NOx Boiler

Chapter 4

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual

Initial Start-Up

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 59 of 170

Table 4-7: Combustion Oxygen Levels for a

100%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

4.8 %

<100 ppm

<100 ppm

14. If necessary, adjust the iris air damper shown in Figure 4-4 until the oxygen level is within

the range specified in Table 4-2.

15. Once the oxygen level is within the specified range at 100%, lower the valve position to

80%.

NOTE

The remaining combustion calibration steps are performed using the
Combustion Cal Menu included in the C-More Control System. The
combustion calibration control functions will be used to adjust the oxygen
level (%) at valve positions of 80%, 60%, 45%, 30% and 20% as described
in the following steps. These steps assume that the inlet air temperature is
within the range of 50°F to 100°F.

16. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter

password 6817 and then press the ENTER key.

17. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu appears

on the C-More display.

18.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

19. Press the CHANGE key. SET Valve Position will begin to flash.

20.

Press the ▲ arrow key until the SET Valve Position reads 80%. Press the ENTER key.

21.

Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.

22. Press the CHANGE key and observe that CAL Voltage 80% is flashing.

23. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-8: Combustion Oxygen Level at

80%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

5.0 %

<100 ppm

<30 ppm

24.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.

25. Once the oxygen level is within the specified range at 80%, press the ENTER key to store

the selected blower output voltage for the 80% valve position.