Appendix c: sensor temperature resistance, Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 127

Advertising
background image

GF-123

Benchmark 2.0LN Low NOx Boiler

Appendix D

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual Reset Ratio Charts

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 127 of 170

APPENDIX C: SENSOR TEMPERATURE RESISTANCE

TABLE C-1: Temperature Sensor Resistance Voltage Chart (Balco)

TEMP (°F)

RES (OHMS)

VOLTS*

-40

-30

-20

-10

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

250

779.0

797.5

816.3

835.4

854.8

874.6

894.7

915.1

935.9

956.9

978.3

1000.0

1022.0

1044.4

1067.0

1090.0

1113.3

1137.0

1160.9

1185.2

1209.5

1234.7

1260.0

1285.6

1311.4

1337.7

1364.2

1391.0

1418.2

1445.7

1.93

1.96

1.99

2.02

2.05

2.07

2.10

2.12

2.15

2.17

2.20

2.23

2.25

2.27

2.30

2.32

2.34

2.36

2.39

2.41

2.43

2.45

2.47

2.50

2.52

2.54

2.56

2.58