*CAUTION!

DO NOT CHANGE the Analog Output Menu Item from its Default setting
(Valve Position 0-10V).

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by Factory-Trained personnel.

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu items in Table 3-6 are used to vary the speed of the
unit’s blower motor based on air temperature and air density at prescribed Air/Fuel Valve
positions (% open). This is accomplished by providing a DC drive voltage to the motor which
adjusts the rotational speed of the blower to maximize combustion efficiency and ensure the unit
conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions specified in
Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.

Table 3-5: Tuning Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Prop Band

1°F

120°F

70°F

Integral Gain

0.00

2.00

1.00

Derivative Time

0.0 min

2.00 min

0.00 min

Reset Defaults?

Yes, No, Are You Sure?

No

Table 3-6: Combustion Cal Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

CAL Voltage 16%

.25

8.20

1.80v

CAL Voltage 30%

.25

8.20

3.20v

CAL Voltage 45%

.25

8.20

3.70v

CAL Voltage 60%

.25

8.20

3.80

CAL Voltage 80%

.25

8.20

4.60

CAL Voltage 100%

.25

8.20

6.00

SET Valve Position

0%

100%

0%

Blower Output

Monitor Blower Output

Voltage

.00