INITIAL START-UP

1. Open the water supply and return valves to

the unit and ensure that the system pumps
are running.

2. Open the natural gas supply valve(s) to the

unit.

3. Set the control panel ON/OFF switch to the

OFF

position.

4. Turn on external AC power to the unit. The

display will show LOSS OF POWER and the
time and date.

5. Set the unit to the Manual Mode by pressing

the AUTO/MAN key. A flashing Manual
Valve Position

message will be displayed

with the present valve position in %. Also,
the MANUAL LED will light.

6. Adjust the air/fuel valve position to 0% by

pressing the ▼ arrow key.

7. Ensure that the leak detection ball valve

down-stream of the SSOV is open.

8. Ensure that the Fuel Selector Switch located

behind the front door of the unit (Figure 4-3)
is in the NATURAL GAS position.

9. Set

the

ON/OFF

switch to the ON position.

10. Change the valve position to 34% using the

▲ arrow key. The unit should begin its start
sequence and fire.

11.

Next, verify that the gas pressure
downstream of the SSOV is 7.3” W.C. for
both FM and IRI gas trains. If gas pressure
adjustment is required, remove the brass
hex nut on the Natural Gas SSOV actuator
containing the gas pressure regulator
(Figure 4-4). Make gas regulator
adjustments using a flat-tip screwdriver to
obtain 7.3” W.C.

12. Increase the valve position to 100% and

verify that the gas pressure downstream of
the SSOV remains at 7.2” W.C. Readjust
pressure if necessary.

13. With the valve position at 100%, insert the

combustion analyzer probe into the flue
probe opening and allow enough time for the
combustion analyzer to settle.

14. Compare the measured oxygen level to the

oxygen range for the inlet air temperature
shown in Table 4-1. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.

Table 4-1

Combustion Oxygen Levels for a 100%

Valve Position

Inlet Air

Temp

Oxygen %

± 0.2

Carbon

Monoxide

NOx

>100°F

5.5 %

<100 ppm

<20 ppm

90°F

5.7 %

<100 ppm

<20 ppm

80°F

5.9 %

<100 ppm

<20 ppm

<70°F

6.0 %

<100 ppm

<20 ppm


FRONT VIEW

ADJUSTABLE

TEMPERATURE

LIMIT SWITCH

FUEL

SELECTOR

SWITCH

RESET BUTTON

FOR MANUAL

TEMPERATURE

LIMIT SWITCH

SEE

DETAIL “A”

DETAIL “A”

Figure 4-3

Front View With Door Removed

4-3