6 low water level fault test, 7 water temperature fault test, Safety device testing – AERCO BMK 2.0 LN Dual Fuel Nov 2010 User Manual

Page 53

Advertising
background image

SAFETY DEVICE TESTING

11. Upon test completion, close the ball valve

and remove the manometer. Replace the
1/8“ plug removed in step 2.

6.6 LOW WATER LEVEL FAULT TEST

To simulate a low water level fault:

1. Set

the

ON/OFF

switch to the OFF position

2. Close the water shut-off valves in the supply

and return piping to the unit.

3. Slowly open the drain valve on the rear of

the unit. If necessary the unit’s relief valve
may be opened to aid in draining.

4. Continue draining the unit until a LOW

WATER LEVEL

fault message is displayed

and the FAULT indicator flashes.

5. Place the unit in the Manual Mode and raise

the valve position above 30%.

6. Set the

ON/OFF

switch to the ON position.

The READY light should remain off and the
unit should not start. If the unit does start,
shut the unit off immediately and refer fault
to qualified service personnel.

7. Close the drain and pressure relief valve

used in draining the unit.

8. Open the water shut-off valve in the return

piping to the unit.

9. Open the water supply shut-off valve to the

unit to refill.

10. After the shell is full, press the LOW

WATER LEVEL RESET

button to reset the

low water cutoff.

11. Press the CLEAR button to reset the

FAULT

LED and clear the displayed error

message.

12. Set the ON/OFF switch to the ON position.

The unit is now ready for operation.



6.7 WATER TEMPERATURE FAULT
TEST

A high water temperature fault is simulated by
adjusting the automatic over-temperature switch.
This switch is accessible from the front of the
unit as shown in Figure 6-2.

Figure 6-2

Temperature Limit Switch Setting

1. Start the unit in the normal operating mode.

Allow the unit to stabilize at its setpoint.

2. Lower the adjustable over-temperature

switch setting to match the displayed
OUTLET TEMPERATURE.

3. Once the adjustable over-temperature

switch setting is approximately at, or just
below, the actual outlet water temperature,
the unit should shut down. The FAULT
indicator should start flashing and a HIGH

6-3

Advertising