SAFETY DEVICE TESTING

10. Since the manual gas shutoff valve is still

closed, the unit will shut down and display
FLAME LOSS DURING IGNITION

following

the IGNITION RETRY cycle.

11. Open the valve previously closed in step 8.

12. Press the CLEAR button. The unit should

restart and fire.

Figure 6-3

Manual Gas Shut-Off Valve Location

6.10 AIR FLOW FAULT TESTS

These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.

1. Disable the blower output drive voltage as

follows:

(d) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(e) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(f) Press

the

▼ arrow key until OFF is

displayed, then press the ENTER key.

2. Start the unit in the Manual Mode at a valve

position of 34%.

3. The unit should shut down and execute an

IGNITION RETRY

cycle by performing the

following steps:

(g) The unit will execute a 30 second re-

ignition delay and display WAIT RETRY
PAUSE.

(h) The unit will then execute a standard

ignition sequence and display WAIT
IGNITION RETRY

.

4. The unit should perform two IGNITION

RETRY

cycles and then shut down on the

third successive ignition attempt. The unit
will display AIRFLOW FAULT DURING
PURGE.

5. Re-enable the blower output drive voltage

by performing the following steps:

(i) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(j) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(k) Press

the

▲ arrow key until VALVE

POSITION 0-10V

is displayed, then

press the ENTER key.

6. Once the unit has proved flame, turn off the

blower by going to the Configuration Menu,
Analog Output

menu item and select OFF.

7. The Blower Proof Switch will open and the

blower should stop. The unit should shut
down and display AIRFLOW FAULT
DURING RUN

.

8. Go to the Configuration Menu, Analog

Output

item and select Valve Position 0-10v.

9. Press the CLEAR button. The unit should

restart.

10. Next, check the Blocked Inlet Switch by first

noting the current position of the Iris Air
Damper and then closing the Damper to
position 8.

11. The unit should shut down and again display

AIRFLOW FAULT DURING RUN

.

12. Return the Iris Air Damper to its previous

setting.

13. Press the CLEAR button. The unit should

restart.