Crown Boiler MWC116ENL User Manual

Page 21

Advertising
background image

19

B. Removing an Existing Boiler From a Common Chimney

Read this only if the MWC boiler is replacing an existing boiler that is being removed from a common

chimney. This section does not apply to the installation of a MWC boiler.

In some cases, when an existing boiler is removed from a common chimney, the common venting system

may be too large for the remaining appliances. At the time of removal of an existing boiler, the following

steps shall be followed with each appliance remaining connected to the common venting system placed

in operation, while the other appliances remaining connected to the common venting system are not in

operation.

(a) Seal any unused openings in the common venting system.

(b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe

condition.

(c) Insofar as practical, close all building doors and windows and all doors between the space in which

all the appliances remaining connected to the common venting system are located and other

spaces of the building. Turn on clothes dryers and any appliance not connected to the common

venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they

will operate at maximum speed. Do not operate a summer exhaust fan. Close fi replace dampers.

(d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust

thermostat so the appliance will operate continuously.

(e) Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use

the fl ame of a match or candle, or smoke from a cigarette, cigar, or pipe.

(f) After it has been determined that each appliance remaining connected to the common venting

system properly vents when tested as outlined above, return doors, windows, exhaust fans,

fi replace dampers and any other gas-burning appliances to their previous condition of use.

(g) Any improper operation of the common venting system should be corrected so the installation

conforms with the National Fuel Gas Code, ANSI Z223.1.

common venting system, the common venting system should be re sized to approach the minimum

size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI

Z223.1.

WARNING

Never common vent a MWC boiler with other appliances.

Natural Gas and Propane Installation Code.

/NFPA 54 and/or CAN/CSA B 149.1

When re-sizing any portion of the

/NFPA 54 and/or CAN/CSA B 149.1

Advertising
This manual is related to the following products: