Crown Boiler MWC116ENL User Manual

Page 55

Advertising
background image

53

The burner may not light on the fi rst try. The most likely cause of this problem on a new installation

is a gas line that has not been completely purged. Other possibilities include inadequate inlet gas
pressure or a boiler that is confi gured for the wrong fuel. If the boiler does not light on the fi rst try, it
will go into a lockout condition. When this happens, the Flame Lockout Lamp (Figure 12.3) will be
illuminated. In addition, Lamps 1 and 3 will fl ash and Lamp 2 will be on continuously. To reset the
boiler, push the Flame Reset Button shown in Figure 12.3 AND rotate the Heating System Knob back
to “0” for a few seconds.

Inspect the fl ame visible through the window. The fl ame should be stable and mostly blue (Fig.12.4).

7)

No yellow tipping should be present; however, intermittent fl ecks of yellow and orange in the fl ame are
normal.

Check the inlet and manifold pressures. To do this, use the following procedure:

8)

Remove the inner cover (fi gure 12.5). Note: this is necessary in order to read the manifold pressure

a)

accurately because the gas valve regulator is referenced to the burner area.

Lamp 2

Lamp 1

Lamp 3

Heating System Knob

DHW

Thermostat

(Combi Only)

Flame Lockout Lamp

Flame Reset Button

Figure 12.3: Control Panel

Figure 12.4: Main Burner Flame

Advertising
This manual is related to the following products: