Crown Boiler MWC116ENL User Manual

Page 69

Advertising
background image

67

Table 15.3: Error Codes

Lamp Number

1 2 3

Flame

L.O.

Lamp

Meaning Corrective

Action

Differential Water Pressure

Switch Failed to Close After

180s

Reset the boiler by turning the Heating System Knob to “0”
for a few seconds, then returning it to its original position.
Then:

Verify that that boiler and system are purged of air

Verify that there is at least 4.5psi at the boiler
gauge

Verify that cirulator is running

Close the throttling valve on the supply more or
install flow restrictor in supply (see piping section)

Failure to Establish Flame

or

Blocked Condensate Trap

or

Reversed Line Voltage

Polarity

(Note: LED #2 will not

illuminate until error has

been present for 4 minutes)

Reset the boiler by turning the Heating System Knob to “0”
for a few seconds then returning it to its original position.
Push Flame Reset Button. Then verify that:

Gas line is purged of air (new installations)

Inlet gas and manifold pressures are correct (see
Start-up Section)

Manifold pressure is correct (see Start-up section)

Electrodes have a gap of 0.149” – 0.157”

Electrodes, flame rod, and wiring are in good
condition

Condensate trap is draining correctly

120VAC exists between the hot (brown)
connection and ground and not between the
neutral (blue) and ground.

Air Pressure Switch Problem

or

Supply Limit Open

or

Flue Gas Limit Open

(Note: LED #2 will not

illuminate until error has

been present for 4 minutes)

Use the flow chart in this section to diagnose the exact
problem.

Defective Supply Sensor

Replace Supply Sensor

Defective DHW Sensor

Replace DHW Sensor

Excessive Temperature on

Primary Circuit

Consult Factory

Consult Factory

Consult Factory

Lamp OFF

Lamp ON

Flashing lamp, alone
or simultaneously
with another lamp.

Flashing lamp,
alternate with
another lamp