XV. Troubleshooting

WARNING

Turn off power to boiler before replacing fuses or working on wiring.

Figure 15.2: Fuse Location

Line Voltage Connections

Fuse

Table 15.1: No Error Code Displayed

CONDITION

POSSIBLE CAUSES

Boiler does not run, no lights are on or fl ashing

• No 120VAC Power at boiler. Check breaker and wiring

between breaker panel and boiler

• Fuse on main PCB is blown (Figure 15.2). Check for short in

boiler wiring, then replace with an idenitcal 4.0A fuse.

Lamp 1 fl ashes every two seconds, but boiler does not
respond to a call for heat.

• Problem with thermostat or zone wiring

Combi boiler does not respond to a call for domestic hot water
(DWH).

• Domestic draw less than 0.5GPM
• Defective fl ow switch (LED inside fl ow switch will glow red

when it resonds to a call for DHW).

• Inlet and outlet connections reversed.

Combi boiler responds to a call for DHW, but hot water output
is inadequate.

• Draw rate is in excess of that shown in Table 2.2
• Inlet and/or manifold pressures incorrect (see Start-up

Section).

• Plate heat exchanger is fouled.
• DHW fi lter is dirty

Boiler responds to a call for heat, but room temperature never
gets high enough to satisfy room thermostat

• Air in radiation
• Inlet and/or manifold pressures incorrect (see Start-up

Section).

• No fl ow, or insuffi ent fl ow, through system.
• Boiler is undersized.
• Insuffi cient radiation

Boiler short cycles AND heat (or DHW) output is inadequate

• Flue gas recirculation into combustion air
• See causes for inadequate heat or DHW above