Neg. pressure tap venturi – Crown Boiler MWC116ENL User Manual

Page 66

Advertising
background image

64

Figure 14.2: Inducer

Neg. Pressure Tap

Venturi

WARNING

Do not leave the boiler in service with the Inner Cover removed.

Do not attempt to fi re this boiler with the Combustion Chamber Cover (Fig. 14.1) removed

Service Notes

Orifi ce Size

1)

– Sea level orifi ce sizes are:

Natural Gas – 1.30 mm

LP Gas – 0.85 mm

Consult your Crown representative for correct orifi ce sizes for use at altitudes above 2000 ft. Orifi ce for this boiler
cannot be drilled in the fi eld.

Operating the Boiler with Inner Cover Removed

2)

– For inspection and troubleshooting purposes, this boiler may

be started and run with the Inner Cover (Figure 12.5) removed.

Pressure Switch

3)

– If necessary, the air pressure switch signal may be read using a slant tube or electronic

monometer connected across the taps on top of the boiler (Figure 14.4). The N.O. contacts on the pressure
switch make, allowing the boiler to fi re, when the switch signal exceeds the “make setting” shown below. Once
the switch is made, the boiler will fi re as long as the pressure at the switch is above the “break setting” shown
below. It is normal for the pressure reading across the switch to drop as the boiler heats up.

Make Setting - 0.64 w.c.

Break Setting - 0.59 w.c.

Limit Reset Buttons

4)

- Manual reset buttons for the fl ue temperature and supply water limits are located on the

top of the boiler as shown in Figure 14.4. To access the buttons, unscrew the plastic covers.