Ii specifi cations, 4table 2.2: ratings, Table 2.3: maximum vent lengths – Crown Boiler MWC116ENL User Manual

Page 6

Advertising
background image

4

Table 2.2: Ratings

MODEL*

APPLICATION

MAX.

INPUT

(BTU/hr)

MINIMUM INPUT (BTU/

hr)

D.O.E.

HEATING

CAPY.

(BTU/hr)

IBR NET

RATING

(BTU/hr)

AFUE

(%)

DHW Output (GPM)

HEATING

DHW

77F Rise 90F Rise

MWC116E*T

Combi

116,000

75,000

49,500

102,000

89,000

85.0

2.67

2.25

MWC116E*L

Heat Only

116,000

75,000

N/A

102,000

89,000

85.0

N/A

N/A

* Insert suffi x “N” for natural gas and “L” for propane. Ratings are the same for both fuels (Example: MWC116ENT denotes Natural
Gas, Combi).

Table 2.3: Maximum Vent Lengths

Using 60/100mm Concentric Vent System Supplied with the Boiler ................................................................25 in.
Using Optional 60/100mm Concentric Vent Components ...............................................................................8ft -10in
Using Optional 80/125mm Concentric Vent Components ................................................................................27 ft

See Vent Section for additional venting options and requirements

II Specifi cations

Figure 2.1: General Confi guration

Table 2.4: Other Specifi cations

Maximum Supply Temperature .............................................176 F
Minimum Continuos Return Temperature .............................86F
Maximum Allowable Working Pressure ................................30 psi
Minimum System Pressure (at boiler ...................................4.4 psi
Maximum Achievable Flow Through Boiler .........................5.5 GPM
Minimum Temperature Rise Across Boiler at High Fire ........37 F
Maximum Gas Inlet pressure ...............................................10.5” Nat / 13.0” LP
Minimum Gas Inlet Pressure ................................................5.3” Nat / 10.5” LP
Electrical Ratings ..................................................................120VAC/60Hz/1.8A
Thermostat Voltage ..............................................................120VAC

Advertising