If the instrument is programmed for Modbus, it can be used as a Modbus RTU slave on a RS485
communication line or on the Ethernet communication line. The Modbus slave adress is defined in the
parameter [Address]. Function code “0x03” and function code “0x10” are supported.

Read

command

Modbus

register

Function

code

Register

address

No. of

registers

Definition

Display value

40 001

03

00,00

00,02

Current display value; Gross or Net

Bit0

Busy

1 – System Busy

Bit1

Data ok

1 – Data ok // 0 – Error

Bit2

Motion

1 – Weight is not stable

Bit3

Net Mode

1 – Net mode

Bit4

Bit5

Bit6

Bit7

Bit8

Bit9

N/A

Bit10

Bit11

Bit12

0 No

Errors

1

ADC out of range

2 ADC

overrange

3 ADC

underrange

4 System

fault

Status 40

003 03 00,02 00,01

Bit13
Bit14
Bit15

Transfer
binary (Bit13
to Bit15) to
decimal and
compare to
error code

5

FT not in weighing mode

Tare weight

40 004

03

00,03

00,02

Current tare weight

Gross Weight

40 006

03

00,05

00,02

Current gross weight

Write

command

Modbus

register

Function

code

Register

address

No. of

registers

Data

byte

count

Data bytes

Definition

00,01 Zero
00,02 Tare
00,03 Clear

Control 40

009 10 00,08 00,01 02

00,04 Print

Modbus exception codes

1 : Function code is not supported
2 : Address is out of range (start and end)
3 : Invalid value feed or wrong byte number
4 : Operation error




















FT-16(D) Technical Manual, Rev. 1.21 December 2008