Installation inspection, Mounting location, Mounting – Carrier AQUAZONE 50RLP User Manual

Page 10: Wiring

Advertising
background image

10

INSTALLATION

Inspection —

Inspect the package contents for visual de-

fects that may have occurred during shipping. If there is any
damage, contact your local representative before proceeding.

Mounting Location —

The Aquazone™ system control

panel should be located indoors. Be sure the location prevents
moisture and rain from coming into contact with the internal
hardware. Avoid areas where excessive moisture, corrosive
fumes, or vapors are present. The ambient temperature range at
the location should be between 32 to 125 F. Do not install the
Aquazone system control panel in electrical interference or
high radio frequency areas. Select a location which will be safe
from water damage and allow sufficient access for service and

wiring. For proper service of the Aquazone system control
panel, the following service clearances are recommended:

Height: 54 in.
Width: 42 in.
Depth: 36 in.

Mounting —

Mount the Aquazone system control panel to

a wall with screws or bolts (not provided). Attach through the
mounting holes provided in enclosure. Provide clearance to
open key-locked access door. Refer to the mounting sheet in-
cluded with the Aquazone system control panel for additional
detailed mounting instructions.

Wiring —

The Aquazone System Control Panel inputs and

outputs are shown in Table 2.

Table 2 — Aquazone System Control Panel Inputs and Outputs

PARAMETER

POWER

INPUT/OUTPUT

TERMINAL

Processor Module

Loop Water Flow

24 vdc

Input

FLOW

System Supply Water Temp.

10 K thermistor

Input

SSWT

System Return Water Temp.

10 K thermistor

Input

SRWT

System Differential Pressure

4-20 mA

Input

SDP

Remote Occupied Mode

24 vdc

Input

RMTOCC

System Shut Down

24 vdc

Input

ALLSYS

Override Input for Zones 1 & 2

24 vdc

Input

OVRIZ1, OVRIZ2

Pump Number 1 & 2 Speeds

4-20 mA

Output

PUMP1, PUMP2

Cooling Tower 1 & 2 Speed/Level

4-20 mA

Output

CTL1, CTL2

Heat Source 1 & 2 Speed/Level

4-20 mA

Output

BLRL1, BLRL2

System Enable for Zone 1 & 2

24 vdc

Output

SYSZ1, SYSZ2

First Optional I/O Module

Override Input for Zone 3 to 10

24 vdc

Input

OVRIZ3 — OVRIZ10

System Enable for Zone 3 to 10

24 vdc

Input

SYSZ3 — SYSZ10

Second Optional I/O Module

Override Input for Zone 11 to 18

24 vdc

Input

OVRIZ11 — OVRIZ18

System Enable for Zone 11 to 18

24 vdc

Input

SYSZ11 — SYSZ18

Pump Control

Occupancy Schedule 1 to 18

Logic

Internal Parameter

Network Global Schedule 65 to 82

Logic

Internal Parameter

Override Input 1 to 18

Logic

Input

OVRIZ1 — OVRIZ18

System Enable Outputs

Logic

Output

SYSZ1 — SYSZ18

Remote Occupied Mode

Logic

Input

RMTOCC

System Differential Pressure

Logic

Input

SDP

System Differential Pressure Set point

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Control Type

Logic

User Configuration

Pump Number 1 & 2 Speeds

Logic

Output

PUMP1, PUMP2

Shut Down Command

Logic

Output

ALLSYS

Heat Rejection Control

System Supply Water Temp.

Logic

Input

SSWT

System Return Water Temp.

Logic

Input

SRWT

System Loop Temperature Set points

Logic

User Configuration

Fluid Cooler/Tower Control

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Cooling Tower 1 & 2 Speed/Level

Logic

Output

CTL1, CTL2

Heat Addition Control

System Supply Water Temp.

Logic

Input

SSWT

System Return Water Temp.

Logic

Input

SRWT

System Loop Temperature Set points

Logic

User Configuration

Boiler Control Type

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Boiler 1 & 2 Speed/Level

Logic

Output

BLRL1, BLRL2