CONFIGURATION

The Aquazone™ System Control Panel contains a Comfort

Controller 6400 programmed using the standard algorithms
and enhanced by BEST++™ custom programming. The
BEST++ Templates for some of the programs have been
removed to prevent field alterations. For other programs,
the templates are included to allow for jobsite customization.
For basic information about the algorithms please refer to the
Comfort Controller Overview and Configuration manual
(808-891). Default configurations are listed later in this section.

Hardware Points —

The hardware points are shown in

Table 11 and 12.

Table 11 — Hardware Points 1 to 32 (HWP01-32)

Table 12 — Hardware Points 33 to 64 (HWP33-64)

LOOP WATER FLOW SWITCH — This discrete input is
used to provide a signal that one of the loop water pumps is on.
If both pumps have been commanded to run and no water flow
is detected, then the system water source heat pumps will
run in the fan only mode for DDC (Direct Digital Control)
coordinated heat pump controllers, while the system relays for
thermostat systems will be turned off.

Loop Water Flow Switch:

Display Units

Discrete ASCII

Default Value

No

Display Range

Yes/No

Network Access

Read/Write

SYSTEM SUPPLY WATER TEMPERATURE — The sys-
tem supply water temperature is the temperature of the water
being pumped to the system of water source heat pumps. The
temperature is measured by a 10K Thermistor (MCI). This
output and sensor is required for proper function of the loop
and heat pumps.

System Supply Water Temperature:

Display Units

degrees F (degrees C)

Default Value

–40.0

Display Range

–40.0-245.0

Network Access

Read/Write

SYSTEM RETURN WATER TEMPERATURE — The sys-
tem return water temperature is the temperature of the water
returning from the system of water source heat pumps. This
temperature measured by a 10K Thermistor (MCI). This output
and sensor is provided for informational purpose and indicates
the average load caused by the normal operation of the heat
pumps.

System Return Water Temperature:

Display Units

degrees F (degrees C)

Default Value

–40.0

Display Range

–40.0-245.0

Network Access Read/Write

SYSTEM WATER PRESSURE — This sensor is used to
measure the pressure of the supply water to the system of water
source heat pumps. This sensor should be located

2

/

3

of the way

down the supply water distribution piping or in a location that
will provide a good reference of the supply water pressure.
This sensor is used to control the speed of variable frequency
drives pumping water to the water source heat pumps. Each
water source heat pump may be equipped with a two position
isolation valve that may be closed when the compressors are
not energized in order to reduce the quantity of water being
pumped through the system.

System Water Pressure:

Display Units

in. wg

Default Value

0.0

Display Range

0.0-5.0

Network Access Read/Write

DESCRIPTION

VALUE

NAME

Loop Water Flow

Yes

FLOW

System Supply Water Temp

60.3 dF

SSWT

System Return Water Temp

51.0 dF

SRWT

System Diff. Pressure

0.00 PSIG

SDP

Remote Occupancy Mode

Off

RMTOCC

System

Enable

ALLSYS

Override Input Zone 1

On

OVRIZ1

Override Input Zone 2

On

OVRIZ2

Pump Number 1 Speed

100.0%

PUMP1

Pump Number 2 Speed

0.0%

PUMP2

Cooling Tower 1 Level

0.0%

CTL1

Cooling Tower 2 Level

0.0%

CTL2

Boiler 1 Level

83.2%

BLRL1

Boiler 2 Level

0.0%

BLRL2

System for Zone 1

Enable

SYSZ1

System for Zone 2

Enable

SYSZ2

Override Input Zone 3

Off

OVRIZ3

Override Input Zone 4

Off

OVRIZ4

Override Input Zone 5

Off

OVRIZ5

Override Input Zone 6

Off

OVRIZ6

Override Input Zone 7

Off

OVRIZ7

Override Input Zone 8

Off

OVRIZ8

Override Input Zone 9

Off

OVRIZ9

Override Input Zone 10

Off

OVRIZ10

System for Zone 3

Disable

SYSZ3

System for Zone 4

Disable

SYSZ4

System for Zone 5

Disable

SYSZ5

System for Zone 6

Disable

SYSZ6

System for Zone 7

Disable

SYSZ7

System for Zone 8

Disable

SYSZ8

System for Zone 9

Disable

SYSZ9

System for Zone 10

Disable

SYSZ10

DESCRIPTION

VALUE

NAME

Override Input Zone 11

Off

OVRIZ11

Override Input Zone 12

Off

OVRIZ12

Override Input Zone 13

Off

OVRIZ13

Override Input Zone 14

Off

OVRIZ14

Override Input Zone 15

Off

OVRIZ15

Override Input Zone 16

Off

OVRIZ16

Override Input Zone 17

Off

OVRIZ17

Override Input Zone 18

Off

OVRIZ18

System for Zone 11

Disable

SYSZ11

System for Zone 12

Disable

SYSZ12

System for Zone 13

Disable

SYSZ13

System for Zone 14

Disable

SYSZ14

System for Zone 15

Disable

SYSZ15

System for Zone 16

Disable

SYSZ16

System for Zone 17

Disable

SYSZ17

System for Zone 18

Disable

SYSZ18