Network time schedule, Holiday schedules – Carrier AQUAZONE 50RLP User Manual

Page 27

Advertising
background image

27

OCCUPIED FROM — This field is used to configure the
hour and minute, in military time, that the mode for the
PremierLink™ controller will switch to occupied.
Occupied From:

Units

Hours:Minutes

Range

00:00 to 24:00
(Minutes 00 to 59)

Default Value

00:00

OCCUPIED TO — This field is used to configure the hour
and minute, in military time, that the mode for the PremierLink
controller switches from occupied to unoccupied.
Occupied To:

Units

Hours:Minutes

Range

00:00 to 24:00
(Minutes 00 to 59)

Default Value

24:00

Table 21 — Occupancy Schedule (OCCPC01)

*User configured.

Network Time Schedule —

The network time schedule

allows the occupancy schedule in another device on the CCN
to control the Aquazone™ system control panel’s occupancy
state.

Each time the occupancy schedule on the controlling device

changes to occupied, the controlling device broadcasts an
occupancy flag over the CCN. To receive an occupancy flag,
a network time created. Up to 18 network time schedules are
configured. The schedules are sequentially named OCCPC65E
to OCCPC82E, however Service Tool or Building Supervisor
software can be used to modify the names up to OCCPC99E.

Holiday Schedules —

A Holiday schedule allows the

user the capability to specify days of the year (holidays) on
which the Aquazone system control panel will follow the
holiday time schedule instead of the normal time schedule for
that day. Holiday time schedules are normally used to program
a weekday in unoccupied mode for the entire day since the
building will be empty during a holiday.

There are 16 different holiday schedules that can be created.

Holiday schedules can also last more than one day, as long as
the days are consecutive.

Holiday schedules must be configured on the time and date

broadcaster element on the CCN. If the Comfort Controller on
the Aquazone system control panel is the broadcaster, it will
send holiday status to all other system elements on the CCN. If
the Comfort Controller is not the broadcaster, do not configure
the holiday schedules for it, as they will not be used.

To configure a holiday schedule, enter a “1” in the Holiday

column of the Day of Week point of the Occupancy schedule.

DESCRIPTION

VALUE

NAME

Time Schedule
Manual Override Hours

0 hours

Ovrd

Period 1: Day of Week

00000000

DOW1

Period 1: Occupied from

00:00

Occ1

Period 1: Occupied to

24:00

UnOcc1

Period 2: Day of Week

00000000

DOW2

Period 2: Occupied from

00:00

Occ2

Period 2: Occupied to

24:00

UnOcc2

Period 3: Day of Week

00000000

DOW3

Period 3: Occupied from

00:00

Occ3

Period 3: Occupied to

24:00

UnOcc3

Period 4: Day of Week

00000000

DOW4

Period 4: Occupied from

00:00

Occ4

Period 4: Occupied to

24:00

UnOcc4

Period 5: Day of Week

00000000

DOW5

Period 5: Occupied from

00:00

Occ5

Period 5: Occupied to

24:00

UnOcc5

Period 6: Day of Week

00000000

DOW6

Period 6: Occupied from

00:00

Occ6

Period 6: Occupied to

24:00

UnOcc6

Period 7: Day of Week

00000000

DOW7

Period 7: Occupied from

00:00

Occ7

Period 7: Occupied to

24:00

UnOcc7

Period 8: Day of Week

00000000

DOW8

Period 8: Occupied from

00:00

Occ8

Period 8: Occupied to

24:00

UnOcc8

Push Button Override

LATCHI00

Name*

Thermostat Override

TEMP_I00

Name*

Time Delay

5 min

Value*

Timed Override Duration

5 min

Value*

Power on Delay

0 sec

PowerUp

Advertising