PUMP 2 RUN TIME — This point displays the number of
hours that the pump has run. When the maximum number of
hours is exceeded (9999 hours), both pumps run time hours
will reset to 0.

Pump 2 Run Time

Display Units

Numeric

Default Value

0

Display Range

0 to 9999

Network Access

Read/Write

Loop Supply Water Set Point —

The low set point

is the low limit the supply water temperature may drop down to
before the heat source will be activated to maintain the Loop
Supply water temperature. The high set point is the high limit
the supply water may rise to before the cooling source will be
activated to maintain the loop supply water temperature. See
Table 15. Set points can also be modified with slide bars in the
ComfortVIEW™ software. See Fig. 11.

Table 15 — Loop Supply Water (SETPT01)

Occupied Low:

Configuration Units

degrees F (degrees C)

Configuration Range

–40.0 to 245.0

Default Value

60.0

Occupied High:

Configuration Units

degrees F (degrees C)

Configuration Range

–40.0 to 245.0

Default Value

90.0

Unoccupied Low:

Configuration Units

degrees F (degrees C)

Configuration Range

–40.0 to 245.0

Default Value

60.0

Unoccupied High:

Configuration Units

degrees F (degrees C)

Configuration Range

–40.0 to 245.0

Default Value

90.0

System Pressure Set Point —

This set point defines

the system pressure that the variable speed pumps will operate
when the Aquazone™ system control panel is configured for
variable speed pumping. See Table 16. Set points can also be
modified with slide bars in the ComfortVIEW software. See
Fig. 12.

Table 16 — System Pressure (SETPT02)

Occupied Low:

Configuration Units

PSIG

Configuration Range

–9999.9 to 9999.9

Default Value

10.0

Occupied High:

Configuration Units

PSIG

Configuration Range

–9999.9 to 9999.9

Default Value

10.0

Unoccupied Low:

Configuration Units

PSIG

Configuration Range

–9999.9 to 9999.9

Default Value

10.0

Unoccupied High:

Configuration Units

PSIG

Configuration Range

–9999.9 to 9999.9

Default Value

10.0

Global Dictionary —

The Global Dictionary table is

shown in Table 17.

Table 17 — Global Dictionary (AQUAMASC)

PUMP CONTROL TYPE — This configuration determines
how the pump outputs will be controlled. If the pump relays
were ordered with the Aquazone system control panel, then the
pump control type should be set to 0. If the pump outputs will
control variable speed pumps, then the configuration should be
set to 1. When variable speed control is selected, both outputs
will control simultaneously.

Pump Control Type:

Configuration Units

None

Configuration Range

0 or 1

Default Value

0

PUMP ROTATION HOURS — When the pump control type
is set to 0 (on/off), this configuration is used to set the maxi-
mum number of hours the lead pump may accumulate beyond
the numbers of hours accumulated for the lag pump. When this
difference in hours is reached, the lead pump will change to the
pump with the lesser number of accumulated run hours.

Pump Rotation Hours:

Configuration Units

HOURS

Configuration Range

0 to 9999

Default Value

50.0

TOWER/COOLING SOURCE CONTROL TYPE — This
configuration determines how the tower outputs will be con-
trolled. If panels were ordered with the stage output transducers,
then tower control type should be set to 0. If the tower outputs
will control variable speed tower fans, then the configuration
should be set to 1.

Variable speed configuration will control both outputs si-

multaneously.

Tower/Cooling Source Control Type:

Configuration Units

None

Configuration Range

0 or 1

Default Value

0

DESCRIPTION

VALUE

NAME

Occupied Lo Setpoint

60.00 df

OccLow

Occupied Hi Setpoint

90.00 df

OccHgh

Unoccupied Lo Setpoint

60.00 df

UnOccLow

Unoccupied Hi Setpoint

90.00 df

UnOccHgh

DESCRIPTION

VALUE

NAME

Occupied Lo Setpoint

10.00 PSIG

OccLow

Occupied Hi Setpoint

10.00 PSIG

OccHgh

Unoccupied Lo Setpoint

10.00 PSIG

UnOccLow

Unoccupied Hi Setpoint

10.00 PSIG

UnOccHgh

DESCRIPTION

VALUE

NAME

PUMPS 0=ON/OFF,1=VFD

0.00

PUMP_CFG

Pump Rotation Hours

50.00

ROT_TIME

TOWERS 0=STAGED,1=VFD

0.00

COOL_CFG

HEAT 0=STAGED,1=MOD/VFD

0.00

HEAT_CFG

Sched Bcst 0=N,1=Y

0.00

GLOBAL