NX-4V2 Control Panel Installation Instructions

Introduction

This is the NX-4V2-Control Panel Installation Instructions.

Installations should only be done by trained professionals. Use

this document to install the system with default settings that

comply with UL requirements.

To install the keypad, other peripherals, and sensors, refer to

the documentation for those devices.

Installation

There are four slots for board insertions inside the metal

enclosure, two on the top and two on the bottom. These allow

the PC board to be positioned vertically (Figure 1 below).

When you slide the board between the grooves of the slots,

make sure the terminal strip is toward the front opening

(toward you) to allow for the wire connections.

Note: Install the metal enclosure with the door opening from

the top to bottom.

Figure 1: Board installation

NetworX keypad maximum wire run

Table 1 below lists wire lengths for one keypad at the end of

the wire. When connecting more than one keypad to the end of

the wire, a higher gauge wire is required

Table 1: Maximum keypad wire run

Length in feet

Wire gauge for NX-
4V2

Wire gauge for NX320-
E

250 24

22

500 20

18

1000 18

16

1500 16

14

2500 14

12

Terminal descriptions

Table 2 below describes the panel terminals.

Table 2: NX-4V2 terminals

Terminal Description

R1

House telephone ring (grey wire on the standard RJ-31X
cord).

R

Telephone ring (red wire on the standard RJ-31X cord).

T

Telephone tip (green wire on the standard RJ-31X cord).

T1

House telephone tip (brown wire on the standard RJ-31X
cord).

AC

AC input. Connect to a 16.5 V 40 or 50 VA Class ll UL
approved transformer.

EARTH

Earth ground. Connect to a cold water pipe or a 6 to 10 ft.
driven rod.

AUX1

Connect negative lead of low current device [relay, LED
(install 1 kohm

resistor in series with LED), etc.]. Connect

positive lead of device to COM. Current is limited to 50
mA when output is negative, and 250 µA when output is
positive.

SIREN

If used as a siren output (default), the speaker rating is 15
watt at 8 or 16 ohms, or 30/40 watt at 4, 8, or 16 ohms. If
voltage output is selected in location 37, this output
becomes voltage output, 12 V, 1 A maximum load. A 3.3
kohm

resistor is required across the bell terminals when a

12 V siren is used. If no resistor is used, you may
experience voltage leakage into the siren, which causes
these devices to output a small signal.

COM

Connect negative wire of powered devices, such as
motion detectors and smoke detectors.

P/N 466-2337 • REV B • January 2011