Cisco XR 12406 User Manual
Page 226

Appendix A Cisco XR 12406 Router Technical Specifications and Warnings
Specifications
A-4
Cisco XR 12406 Router Installation Guide
OL-13831-01
Caution
Exhaust from other equipment vented directly into the Cisco XR 12406 Router air
inlet may cause overheating. Install the router so that it is protected from a direct
flow of hot air from other equipment.
Table A-4
Cisco XR 12406 Router Environmental Specifications
Description
Value
Temperature
32° to 104°F (0° to 40°C) operating
–4° to 149°F (–20° to 65°C) non-operating
Humidity
10 to 90% noncondensing operating
5 to 95% noncondensing non-operating
Altitude
0 to 10,000 ft. (0 to 3,050 m) operating
0 to 30,000 ft. (0 to 9,144 m) non-operating
Heat dissipation
5,828 Btu/hr maximum (AC original series)
8,871 Btu/hr maximum (AC enhanced series)
5,562 Btu/hr maximum (DC original series)
8,871 Btu/hr maximum (DC enhanced series)
Cooling
Facing the router, right-side-to-back cooling
Shock
5 to 500 Hz, 0.5g
1
(0.1 oct/min
2
) operating
5 to 100 Hz, 1g (0.1 oct/min) non-operating
100 to 500 Hz, 15g (0.2 oct/min)
500 to 1,000 Hz, 1.5g (0.2 oct/min)
1.
g = Gravity
2.
oct/min = Octave per minute