3.4

Wiring the Gateway LER Field Port to a LonWorks network

Connect the Gateway to the field network with the LonWorks terminal using a twisted pair non-shielded

cable. LonWorks has no polarity.

3.5

Power-Up the Gateway RER or LER

Apply power to the device. Ensure that the power supply used complies with the specifications provided in
Appendix C.1. Ensure that the cable is grounded using the “Frame-GND” terminal. The Gateway is factory set for
9-30VDC or 12-24 VAC. Voltage Pinouts

3.6

Commissioning the Gateway-LER on a LonWorks network

Commissioning may only be performed by the LonWorks administrator.

To commission the Gateway LER LonWorks port, insert a small screwdriver in the commissioning hole on the face
of the LER’s enclosure to access the Service Pin. See the illustration on the Gateway LER as to which way to toggle
the screw driver during commissioning.