LAARS Gateway Startup Guide

Page 22 of 32

LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA

Web:

www.laars.com

Toll Free: (800) 900-9276

Appendix B.

Vendor Information

Appendix B.1.

Default Modbus COM Settings for Mascot II, NeoTherm, and NeoTherm LC

Serial Port Setting

Mascot II

NeoTherm NeoTherm LC

Baud Rate

38.4

38.4

38.4

Data Bits

8

8

8

Stop Bits

1

1

1

Parity

None

None

None

Modbus RTU Node_ID: 1 through 8 Boilers 1 through 8 1 through 8

1 through 8

Appendix B.2.

Gateway RER: DIP switch settings for Mascot II BACnet MSTP/IP or Mascot II, NeoTherm,

and NeoTherm LC to support 1 through 8 boilers to Modbus TCP

Note: The lid on top of the Gateway has to be removed in order to select the A Bank of DIP switches. Pull on
the lid while holding on to the 6 pin Phoenix connector. Please do not hold the wall mount tabs as these are
designed to break off if not required!

To set select these configurations, open the Gateway and select the A bank of switches (A1 or A2 or A3)

on the small ProtoCessor module that sits on top of the ProtoCarrier (inside the Gateway).

Gateway RER

Gateway S Bank DIP Switches ProtoCessor A Bank DIP Switches

Profile – FPC-N34

S0

S1

S2

S3

A1 A2 A3 A4 A5 A6 A7 A8

Modbus TCP Sola 1 Off

Off

Off

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 2 On

Off

Off

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 3 Off

On

Off

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 4 On

On

Off

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 5 Off

Off

On

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 6 On

Off

On

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 7 Off

On

On

Off

On Off Off Off Off Off Off Off

Modbus TCP Sola 8 On

On

On

Off

On Off Off Off Off Off Off Off

S Bank DIP Switches

A1, A2, A3 DIP Switches