The LAARS Gateway LER and RER Startup Guide

Page 23

LAARS Gateway Startup Guide

Page 23 of 32

LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA

Web:

www.laars.com

Toll Free: (800) 900-9276

Appendix B.3.

Mascot II, NeoTherm and NeoTherm LC Modbus RTU Mappings to BACnet MS/TP,

BACnet IP, Metasys, and LonWorks

Point Name

BACnet

Object

Id

BACnet

Object

Instnace

Metasys N2

Data Type

Metasys

Point

Address

Lon Name

Lon SNVT Type

Demand source AI

1

AI

1

nvoXDemSrc SNVT_count_inc_f

Outlet sensor AI

2

AI

2

nvoXOutletSensor SNVT_count_inc_f

Firing rate

AI

3

AI

3

nvoXFiringRate SNVT_count_inc_f

Fan speed

AI

4

AI

4

nvoXFanSpeed SNVT_count_inc_f

Flame signal

AI

5

AI

5

nvoXFlameSignal SNVT_count_inc_f

Inlet sensor

AI

6

AI

6

nvoXInletSensor SNVT_count_inc_f

DHW sensor AI

7

AI

7

nvoXDHWSensor SNVT_count_inc_f

S5 sensor

AI

8

AI

8

nvoXS5Sensor SNVT_count_inc_f

Stack sensor AI

9

AI

9

nvoXStackSensor SNVT_count_inc_f

4 - 20 mA remote ctl

input

AI

10

AI

10

nvoXRemCtlInput SNVT_count_inc_f

Active CH setpoint AI

11

AI

11

nvoXAct_CH_SP SNVT_count_inc_f

Active DHW setpoint AI

12

AI

12

nvoXAct_DHW_SP SNVT_count_inc_f

Active LL setpoint AI

13

AI

13

nvoXAct_LL_SP SNVT_count_inc_f

Analog modulation

input

AI

14

AI

14

nvoXAnaModInput SNVT_count_inc_f

Burner control status AI

15

AI

15

nvoXBrnrCtlStat SNVT_count_inc_f

Lockout code AI

16

AI

16

nvoXLockoutCode SNVT_count_inc_f

Alarm reason AI

17

AI

17

nvoXAlmReason SNVT_count_inc_f

Hold code

AI

18

AI

18

nvoXHoldCode SNVT_count_inc_f

CH status

AI

19

AI

19

nvoXCH_Status SNVT_count_inc_f

CH setpoint source AI

20

AI

20

nvoXCH_SP_Src SNVT_count_inc_f

CH heat demand AI

21

AI

21

nvoXCH_HeatDmnd SNVT_count_inc_f

CH burner demand AI

22

AI

22

nvoXCH_BrnrDmnd SNVT_count_inc_f

CH requested rate AI

23

AI

23

nvoXCH_ReqRate SNVT_count_inc_f

DHW status AI

24

AI

24

nvoXDHW_Status SNVT_count_inc_f

DHW Priority Count AI

25

AI

25

nvoXDHW_PriCnt SNVT_count_inc_f

DHW heat demand

AI

26

AI

26

nvoXDHW_HeatDmn

d

SNVT_count_inc_f

DHW burner demand

AI

27

AI

27

nvoXDHW_BrnrDmnd SNVT_count_inc_f

DHW requested rate

AI

28

AI

28

nvoXDHW_ReqRate SNVT_count_inc_f

DHW pump status AI

29

AI

29

nvoXDHW_PmpStat SNVT_count_inc_f

DHW Pump Idle Days

Count

AI

30

AI

30

nvoXDHW_PpIdDyCt SNVT_count_inc_f

System pump status AI

31

AI

31

nvoXSysPmpStatus SNVT_count_inc_f

System Pump Idle

Days Count

AI

32

AI

32

nvoXSysPmpIdDyCt SNVT_count_inc_f

Boiler pump status AI

33

AI

33

nvoXBlrPmpStatus SNVT_count_inc_f

Boiler Pump Idle

Days Count

AI

34

AI

34

nvoXBlrPmpIdDyCt SNVT_count_inc_f

Burner run time AV

35

AO

35

nviX/nvoXBrnrRunTi

me

SNVT_count_inc_f

DHW pump cycle

count

AV

36

AO

36

nviX/nvoXDHWPmpC

ycCnt

SNVT_count_inc_f

System pump cycle

count

AV

37

AO

37

nviX/nvoXSysPmpCyc

Cnt

SNVT_count_inc_f

Boiler pump cycle

AV

38

AO

38

nviX/nvoXBlrPmpCyc

SNVT_count_inc_f