NOTE: When setting DIP Switches, please ensure that power to the board is OFF.

2.3.2

Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP & Metasys N2

DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the

Building Management System for BACnet MS/TP.

Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.

B0 B1 B2 B3

Figure 2: B0 – B3 DIP Switches

2.3.2.1

Baud Rate DIP Switch Selection

Baud B0 B1 B2 B3
9600

On On On Off

19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On

2.3.3

Using S0 – S3 bank of DIP Switches to select and load Configuration Files

The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of

pretested/preloaded configuration files which are stored in the Gateway RER (BACnet MS/TP, BACnet/IP
and Metasys N2) and LER (LonWorks).

S0 S1 S2 S3

Figure 3: S0 – S3 DIP Switches

2.3.3.1

S0 – S3 DIP Switch Configuration Settings

A.

BACnet MS/TP, BACnet/IP and N2 for the Mascot II, NeoTherm, and NeoTherm LC

S Bank DIP Switches

H2355100A