The LAARS Gateway LER and RER Startup Guide

Page 25

LAARS Gateway Startup Guide

Page 25 of 32

LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA

Web:

www.laars.com

Toll Free: (800) 900-9276

Appendix C.

Reference

Appendix C.1.

Specifications

Gateway RER

Gateway LER

Electrical

Connections

One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One 3-pin RS-485 Phoenix connector, one
RS-485 +/- ground port
One Ethernet-10/100 Ethernet port

One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One Ethernet 10/100 BaseT port
One FTT-10 LonWorks port

Approvals

CE (EN55022;EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conformance Tested,
OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked

LonMark Certified

Power

Requirements

Multi-mode power adapter: 9-30VDC or 12 - 24VAC

Physical

Dimensions

11.5 cm L x 8.2 cm W x 4.0 cm H (4.5 x 3.2 x 1.6 in.)

Weight

0.2 kg (0.4 lbs)

Operating

Temperature

-40°C to 75°C (-40°F to167°F)

Surge

Suppression

EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT

Humidity

5 - 90% RH (non-condensing)

(Specifications subject to change without notice)

Appendix C.1.1.

Compliance with UL Regulations

For UL compliance, the following instructions must be met when operating the Gateway.

The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating

temperature range.

The interconnecting power connector and power cable shall:

Comply with local electrical code

Be suited to the expected operating temperature range

Meet the current and voltage rating for the Gateway/Net

Furthermore, the interconnecting power cable shall:

Be of length not exceeding 3.05m (118.3”)

Be constructed of materials rated VW-1 or FT-1 or better

If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be

installed in a Restricted Access Area requiring a key or a special tool to gain access.

This device must not be connected to a LAN segment with outdoor wiring.