Model and

Gas Type

Distance from Gas Meter or Last Stage Regulator

0-100'

0-31 m

100-200'

31-61m

200-300'

61-91m

199 natural

1¼"

3.2 cm

1¼"

3.2 cm

1¼"

3.2 cm

199 propane

1"

2.5 cm

1"

2.5 cm

1¼"

3.2 cm

300 natural

1¼"

3.2 cm

1½"

4.0 cm

1½"

4.0 cm

300 propane

1

2.5 cm

1¼"

3.2 cm

1¼"

3.2 cm

399 natural

1¼"

3.2 cm

1½"

4.0 cm

2"

5.0 cm

399 propane

1¼"

3.2 cm

1¼"

3.2 cm

1½"

4.0 cm

Notes:

1. These figures are based on 1/2" (0.12 kPa) water column pressure drop.

2. Check supply pressure and local code requirements before proceeding with work.

3. Pipe fittings must be considered when determining gas pipe sizing

.

Table 7. Gas Piping Size.

SECTION 3.

Gas Supply and Piping

3.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The Mighty Stack’s gas train allows the user to

pipe the gas from either the right side or the left side

of the unit. As shipped, the right side of the gas train is

capped off, and there is a manual valve on the left side.

If desired, the manual valve on the left side of the gas

train may be moved to the right side, and the cap on

the right side may be moved to the left.

Review the following instructions before

proceeding with the installation.

1. Verify that the appliance is fitted for the proper

type of gas by checking the rating plate. Mighty

Stack appliances are equipped to operate at

elevations up to 10,000 feet (3050m). Mighty

Stack appliances may be adjusted to operate

properly at altitudes above 2500 feet (see Section

6.5.2) and the input will be reduced if the heating

value of the gas supply is below sea level values.

2. The maximum inlet gas pressure must not

exceed 13" w.c. (3.2kPa). The minimum inlet gas

pressure is 5 in. w.c. (1.2 kPa).

3. Refer to Table 7, size supply.

4. Run gas supply line in accordance with all

applicable codes.

5. Locate and install manual shutoff valves in

accordance with state and local requirements.

6. A sediment trap must be provided upstream of

the gas controls.

7. All threaded joints should be coated with

piping compound resistant to action of liquefied

petroleum gas.

8. The appliance and its individual shutoff valve

must be disconnected from the gas supply piping

during any pressure testing of that system at test

pressures in excess of 0.5 psig (3.45 kpa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas

supply piping system at test pressures equal to or

less than 0.5 psig (3.45 kpa).

10. The appliance and its gas connection must be

leak tested before placing it in operation.

11. Purge all air from gas lines.

WARNING

Do not use open flame to check for leaks. An open

flame could lead to explosion, which could result in

property damage, serious injury or death.

AVERTISSEMENT

Ne recherchez pas les fuites avec une flamme nue.

Une flamme nue peut provoquer une explosion qui

peut causer des dommages matériels, de sérieuses

blessures corporelles ou la mort.

NOTE: The Mighty Stack appliance and all other

gas appliances sharing the gas supply line must

be firing at maximum capacity to properly measure

the inlet supply pressure. The pressure can be

measured at the supply pressure port on the gas

valve. Low gas pressure could be an indication of

an undersized gas meter, undersized gas supply

lines and/or an obstructed gas supply line.