LAARS Mighty Stack MS-080 (Sizes 199, 300, 399) - Install and Operating Manual User Manual

Page 21

Advertising
background image

Mighty Stack

Page 21

Figure 8. Logic Diagram, ON/OFF Water Heater.

control (F1 and F2). The ignition control will remain

in this fault mode, with the blower off. If the power to

PSW is removed while there is still a call for heat, the

ignition sequence will start again, but the main valves

will not be energized until PSW sees power during the

ignition sequence.

At the start of an ignition sequence, the control

sends the combustion blower output (F1 and F2). If

the control does not see power at PSW for more than

30 seconds, the control will remain in this fault mode,

with the blower on. If proper airflow is later detected

on PSW, the control begins a pre-purge and a normal

trial for ignition.

If the PSW signal is lost while the Mighty Stack

is firing, the control will immediately de-energize the

gas valve terminal (MV). The blower will remain on

for the post-purge period (45 seconds), and the control

will continue to monitor the PSW input. If the signal

is detected during the post-purge period, a normal trial

for ignition will begin, starting with the 15-second

pre-purge. If the signal is not detected during the post-

purge, the control will lockout with the blower off.

6.6 Operating the Burner and Set-Up

6.6.1 Set-Up for 0 to 2500 Feet Altitude

The setup must be checked before the unit is put in

operation. Problems such as failure to start, rough igni-

tion, strong exhaust odors, etc. can be due to improper

setup. Damage to the Mighty Stack resulting from

improper setup is not covered by the limited warranty.

1. Using this manual, make sure the installation

is complete and fully in compliance with the

instructions.

2. Determine that the appliance and system are

filled with water and all air has been bled from

both. Open all valves.

3. Observe all warnings on the Operating

Instructions label and turn on gas and electrical

power to appliance.

4. Switch on the appliance power switch located on

the right side of the unit.

5. The Mighty Stack will enter the start sequence,

as long as the unit is being called for heat. The

blower and pump come on for pre-purge, then

the ignitor warm-up sequence starts and after

the ignitor warm-up is complete and all safety

devices are verified, the gas valves open. If

ignition doesn’t occur, check that there is proper

gas supply. Wait 5 minutes and start the unit

again. During initial start up, air in the gas line

may cause the Mighty Stack to "lock out" during

the first few trials for ignition. If the ignition

control locks out, reset by cycling the power off

and on using the main power switch on the right

side of the cabinet.

6. When the unit is running, the supply gas pressure

must be checked. Inlet gas pressure must not

exceed 13 in. w.c. (3.2 kPa). The minimum inlet

gas pressure is 5 in. w.c. (1.2 kPa) and 8 in. w.c.

(2 kPa) for LP.

7. Once the inlet gas pressure is verified, the outlet

gas pressure (manifold gas pressure) must be

checked, and adjusted, if necessary. The manifold

gas pressure must be 3.0 in. w.c. (0.62 kPa) for

natural gas and 9.0 in. w.c. (2.2 kPa) for LP.

8. Complete the setup by checking the CO

2

at the

outlet of the unit. The CO

2

should be 8% for

natural gas, or 9.2% for LP.

Advertising