SECTION 5.

Electrical Connections

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirements, with the latest edition of the National

Electrical Code, ANSI/NFPA 70, in the U.S. and

with latest edition of CSA C22.1 Canadian Electrical

Code, Part 1, in Canada. Do not rely on the gas

or water piping to ground the metal parts of the

water heater. Plastic pipe or dielectric unions may

isolate the water heater electrically. Service and

maintenance personnel, who work on or around

the water heater, may be standing on wet floors

and could be electrocuted by an ungrounded water

heater.

AVERTISSEMENT

L’appareil doit être relié à la terre conformément

aux exigences de la réglementation locale ou,

en l’absence d’une telle réglementation, à la plus

récente édition du National Electrical Code (Code

national de l’électricité) ANSI/NFPA 70 aux États-

Unis, et à la plus récente édition du Code Canadien

de l’électricité 1

ère

partie (Canadian Electrical

Code Part 1) CSA C22.1, au Canada. N’utilisez

pas les tuyauteries d’eau ou de gaz pour mettre

à la terre les pièces métalliques de la chaudière;

des tuyauteries en plastique ou des raccords

union diélectriques peuvent isoler électriquement

la chaudière. Les employés qui sont appelés à

travailler sur la chaudière ou autour peuvent être

électrocutés par une chaudière qui n’est pas mise à

la terre.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

NOTE: All internal electrical components have been pre-

wired. No attempt should be made to connect electrical

wires to any other location except the wiring box.

5.1 Main Power

Connect a 15 amp. fused, 120-volt supply to

the main power switch. Both hot and neutral wires

are provided for connections inside the water heater

jacket. Ground wire can be connected to the grounding

screw in the box.

Wiring diagram is shown in Figure 7.

5.2 Field Wiring

Other Field Interlocks: To install other field-

wired switches (proving switches, flow switches, etc.),

remove the jumper between the terminals labeled “3”

and “4” (see Figure 6).

Figure 6. Terminal Block.