LAARS Mighty Stack MS-080 (Sizes 199, 300, 399) - Install and Operating Manual User Manual

Page 25

Advertising
background image

Mighty Stack

Page 25

sensors from all components that are attached to

the inlet/outlet header.

4. Isolate the heat exchanger from the water supply.

5. Disconnect the header flanges from the inlet and

outlet.

6. Allow the heat exchanger to drain. Remove the

venting and remove the top, by removing the

screws that attach the top to the side panels.

Remove the side panels.

7. Remove the heat exchanger from the unit.

NOTE: Heat exchangers are heavy and may

require two people to remove to avoid personal

injury.

8. Clean the heat exchanger: A light accumulation

of soot or corrosion on the outside of the heat

exchanger can be easily removed. Use a wire

brush to remove loose soot and scale from the

heat exchanger.

9. NOTE: While the heat exchanger is out of the

unit, inspect the firewall refractory insulation.

Replace if necessary.

10. Inspect the inside of the copper tubes for scale

buildup. Scale can build up on the inner surface

of the heat exchanger tubes, which can restrict

water flow. If the tubes show signs of scaling,

clean the internal surface.

11. Reassemble in the reverse order, and check

appliance operation after start-up.

NOTE: The warranty does not cover damage due to

lack of maintenance, lack of water flow, inadequate

water temperature, or improper operating practices

outlined in this manual.

Advertising