LAARS Mighty Stack MS-080 (Sizes 199, 300, 399) - Install and Operating Manual User Manual

Page 16

Advertising
background image

Laars Heating Systems

Page 16

SECTION 4.

Water Connections

4.1 Water System Piping

Pipe the outlet from the heater’s relief valves

such that any discharge from the 2 relief valves will be

conducted to a suitable place for disposal when relief

occurs. Do not reduce line size or install any valves in

this line. The lines must be installed to allow complete

drainage of both the valve and the line (see Figure 4).

The minimum inlet water temperature for the

Mighty Stack is 120°F (49°C) to avoid condensing on

the copper coils. It is the responsibility of the installer

to properly mix supply water as necessary to keep the

return water temperature above 120°F.

NOTE: Laars will not warranty claims for failure to

provide minimum return water temperature.

4.2 Hot Water Supply Piping

If the Mighty Stack water heater is installed in

a closed water supply system, such as one having a

backflow preventer in the cold water supply line, the

relief valve may discharge periodically, due to thermal

expansion. Means (such as a properly-sized expansion

tank) shall be provided to control thermal expansion.

Contact the water supplier or local plumbing inspector

on how to control this situation.

4.3 Water Flow Requirements

In a water heating application, new water is

constantly being introduced. With the new water

comes a fresh supply of minerals that can be deposited

on the unit’s heat exchanger. This is commonly known

as scaling. The amount of minerals will depend

upon the hardness of the water. Water can also be

aggressive, and can erode metals, including copper,

if the water is moved too quickly. The water flow

requirements for the Mighty Stack water heater are

based upon the hardness of the water. The water flow

is kept high enough to prevent scaling, but low enough

to prevent tube erosion. For extremely soft or hard

water, cupro-nickel tubes are available. Contact a

Laars representative if you have questions or concerns

about water quality.

Water heaters can be ordered with a standard

pump for soft or normal water or with a pump for

hard water. The pumps used are sized for the head loss

through the heater.

4.4 Combined Water Heating (potable)

and Space Heating

NOTE: These systems are not allowed in the

Commonwealth of Massachusetts.

Piping and components connected to this water

heater shall be suitable for use with potable water.

Toxic chemicals, such as used for water heater

treatment, shall not be introduced into the potable

water used for space heating.

This water heater shall not be connected to any

heating system or component(s) previously used with a

non-potable water heating appliance.

When the system requires water for heating at

temperatures higher than required for other uses,

an anti-scald mixing or tempering valve shall be

installed to temper the water for those uses in order

to reduce scald hazard potential.

4.5 Freeze Protection

Although Mighty Stack water heaters are design-

certified for outdoor installations, such installations

are not recommended in areas subject to freezing

temperatures, unless proper precautions are taken.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,

etc., may prevent a heater from firing. Any time a

heater is subjected to freezing conditions, and the

heater is not able to fire, and/or the water is not

able to circulate, there is a risk of freezing in the

heater or in the pipes in the system. When water

freezes, it expands. This can result in bursting of pipes

in the system, or damage to the heater, which could

result in leaking or flooding conditions.

Contact the local factory representative or Laars

for additional information.

Advertising