Figure 2. Combustion Air and Vent Through Roof.

SECTION 2.

Venting and Combustion Air

WARNING

For indoor installations, as an additional measure

of safety, Laars strongly recommends installation of

suitable Carbon Monoxide detectors in the vicinity of

this appliance and in any adjacent occupied spaces.

AVERTISSEMENT

Pour des installations intérieures, Laars

recommande fortement, comme mesure de sécurité

supplémentaire, l’installation de détecteurs de

monoxyde de carbone adaptés dans le voisinage

de l’appareil et dans chacune des pièces habitées

adjacentes.

2.1 Combustion Air

Mighty Stack water heaters must have provisions

for combustion and ventilation air in accordance with

the applicable sections addressing requirements for air

for combustion and ventilation of the National Fuel

Gas Code, ANSI Z223.1. In Canada, the applicable

sections of the Natural Gas and Propane Installation

Code (CSA B149.1) must be followed. In all cases any

and all applicable local installation codes must also be

followed.

A Mighty Stack appliance may receive

combustion air from the space in which it is installed,

or it can be ducted directly to the unit from the outside.

Proper ventilation air must be provided in either case.

2.1.1 Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of

the same cross-sectional area as the free area of the

openings to which they connect.

Method 1: Two permanent openings, one

commencing within 12 inches (30 cm) of the top

and one commencing within 12 inches (30 cm) of

the bottom, of the enclosure shall be provided. The

openings shall communicate directly, or by ducts,

with the outdoors or spaces that freely communicate

with the outdoors. When directly communicating

with the outdoors, or when communicating to the

outdoors through vertical ducts, each opening shall

have a minimum free area of 1 square inch per 4000

Btu/hr (5.5 square cm/kW) of total input rating of all

equipment in the enclosure. When communicating to

the outdoors through horizontal ducts, each opening

shall have a minimum free area of not less than

1 square inch per 2000 Btu/hr (11 square cm/kW) of

total input rating of all equipment in the enclosure.

Table 3 shows data for this sizing method, for each

Mighty Stack model.

Method 2: One permanent opening, commencing

within 12 inches (30 cm) of the top of the enclosure,

shall be permitted. The opening shall directly

communicate with the outdoors or shall communicate

through a vertical or horizontal duct to the outdoors

or spaces that directly communicate with the outdoors

and shall have a minimum free area of 1 square inch

per 3000 Btu/hr (7 square cm/kW) of the total input

rating of all equipment located in the enclosure. This

opening must not be less than the sum of the areas of

all vent connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform

to the requirements in the applicable codes listed

above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow CSA

B149.1, the Natural Gas and Propane Installation Code.

Size

Each Opening*

Square inches

Square cm

199

50

323

300

75

484

399

100

645

*Net Free Area in Square Inches / Square cm

Area indicated is for one of two openings; one at floor level

and one at the ceiling, so the total net free area could be

double the figures indicated.
This chart is for use when communicating directly with the

outdoors. For special conditions and alternate methods, refer

to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of

louvers. Correct for screen resistance to the net free area

if a screen is installed. Check all local codes applicable to

combustion air.

Table 3. Combustion Air Openings.