U.h.e service manual page 19 – LAARS U.H.E. - Service Manual User Manual

Page 19

Advertising
background image

U.H.E Service Manual

Page 19

Refer to ignition module illustration below,

is there 24VAC between

P3(2) and P3(5) (blue and

brown wires) during the flame establishing period?

(Note: Valve LED must be lit during this check)

Y

Replace

ignition module.

(see page 34)

N

Replace Rectifier harness and/or

gas valve.

(see page 24)

N

Y

Does flame LED on the module

light and stay lit?

Can you hear or feel

gas valve energize?

Does burner light

smoothly, without

evidence of coughing

or huffing?

Y

N

Check for obstruction

at inlet of gas valve.

Is inlet free of

obstruction?

Check flame sensor,

Is there 1 to 5 micro amps

(min.) during 1.5 second

flame proving period?

(see page 32)

N

Y

IGNITION MODULE

Continued from

previous page

N

Call for technical

support

Clear obstruction

Observe burner operation through the sight glass located on the combustion insert mounting flange. Normal burner operation

should ignite smoothly, without evidence of coughing or huffing upon ignition. The burner flame should be a blue flame near the

burner surface in a uniform flame pattern. Occasional yellow or white streaks are normal.

Y

Does burner operate

normaly until thermostat is

satisfied?

N

System OK

Y

Turn VENTURI set screw clockwise until its

bottomed out. Turn screw counter-clockwise 6-½

turns from bottom (see illustration below). Note:

UHE100T399 models do not have a venturi screw.

The gas regulator setting should be 1 - 1 ¼ turns

out from bottom.

Replace flame sensor

(see page 32)

Inspect burner tube, (see page 22)

N

Y

N

WARNING

120 volt potential exposure. Isolate the

appliance and reconfirm power is

disconnected using a multi-meter.

Y

Venturi

adjustment

Inlet gas

pressure tap

UHE100T399

Only

Gas valve

regulator

19