Vent Tables

Notes:

1) Multiply the total number of 90° elbows (intake and exhaust) by 5 feet. Do not include the

termination fittings or 3" condensate elbow.

2) Multiply the total number of 45° elbows (intake and exhaust) by 2 ½ feet.

3) Add this to the total length of straight pipe - intake and exhaust.

4) The sum total of all elbows and straight pipe - intake and exhaust must not exceed maximum

lengths from tables above.

Example: UHE100T199

A 3" Balanced Direct vent system has 30 feet of straight exhaust pipe and 30 feet of straight intake pipe.

It has 3- 90° elbows in the exhaust and 3- 90° elbows in the intake. It has 1- 45° elbow in the exhaust and

1- 45° elbow in the intake.

Therefore:

6- 90° elbows x 5 feet = 30 feet.

2- 45° elbows x 2½ feet = 5 feet.

60 feet of straight pipe + 30 feet + 5 feet = 95 feet.

System is within “Maximum Combined Length” from table above.

Unbalanced Direct Vent Systems

Air intake CAN NOT exceed exhaust

by more than 30 feet

Power Vented Systems

PVC, CPVC

Total length of exhaust piping must not exceed

“Maximum Vent Length”

Shown below

Maximum Vent Length (feet)

Model Number

3"

UHE60T125, UHE100T150

120'

UHE60T150, UHE100T199

UHE60T199

UHE100T300

100'

80'

60'

4"

170'

150'

130'

110'

UHE100T399

50'

100'

Balanced Direct Vent Systems

PVC, CPVC

Total length of intake piping and exhaust piping

added together must not exceed “Maximum

Combined Length”

Shown below

Maximum Combined Length (feet)

Model Number

3"

UHE60T125, UHE100T150

120'

UHE60T150, UHE100T199

UHE100T250

UHE100T300

100'

80'

60'

4"

170'

150'

130'

110'

UHE100T399

50'

100'

7

UHE60T199

80'

130'

UHE100T250

80'

130'