Hot Surface Ignition Models:

Are safety circuits in normal position?

Does blower

energize?

Is there 120VAC

across the white and

black wires at the

blower?

(see photo at right)

Replace blower.

(see page 25)

Y

N

Refer to ignition module/

control board illustration.

Is there 120VAC between

P5(1) and P5(3)?

Repair/replace

wire harness.

Y

Replace ignition module/

control board.

Y

N

N

Y

N

N

Is there 120VAC

across the white and

black wires at the

terminal block ?

Hot Surface Ignition

Models ONLY:

Refer to ignition

module, is there 24

VAC between

P3(7)

and ground?

Y

N

Thermostat not

calling for heat.

(see page 12)

Correct safety circuit problem per

safety circuit trace

(see page 27).

Y

Y

Is there 120VAC

across the white and

black wires at the

terminal block ?

(see photo at right)

N

N

Refer to ignition module/control board

illustration. Is there 120VAC between

P5(1) and

P5(3)?

Y

Replace

ignition module/

control board.

Call technical

support.

Check amp draw through

BLACK wire lead of blower

motor. Is there .6 to 3.0

amps?

Replace blower.

(see “Blower Replacement

Procedure”)

N

Y

Is Blower wheel secured to

blower motor shaft?

N

Y

Determine

power

source

problem

and

correct

25

Black wire leading to

blower motor looped

through amprobe.

120VAC check at

Terminal Block

Checking for 120VAC

(Black & White Wires)