Check exhaust tube pressure, Exhaust pressure switch testing and replacement, Laars heating systems – LAARS U.H.E. - Service Manual User Manual

Page 28

Advertising
background image

LAARS Heating Systems

Page 28

Check Exhaust Tube Pressure

Exhaust Pressure Switch Testing and Replacement

Exhaust Tube

pressure tap location

Exhaust tube

at bottom of heater

N

Replace

blocked vent switch.

(see page 29)

Is exhaust venting

system blocked or

obstructed? Also

check condensate

elbow and drain.

Clear obstruction.

Determine cause

and correct.

Y

Is vent system total

length compliant with

vent tables in the

instruction manual?

Reconfigure vent

system to be

compliant with

vent tables (see

“Specifications”).

Y

N

With monometer, take a

reading at the

exhaust

tube pressure tap location.

Is value negative (-) or

slightly postitive

(see illustration below).

Y

N

With ohmmeter check

pressure switch for

continuity. Contacts should

be closed.

Y

N

Pressure switch O.K.

28

Is pressure in exhaust tube near 2.7" w.c. or more? If so, correct

blockage (above). If exhaust pressure is low (0.40" or less), replace

pressure switch.