Check exhaust tube pressure, Exhaust pressure switch testing and replacement, Laars heating systems – LAARS U.H.E. - Service Manual User Manual
Page 28
LAARS Heating Systems
Page 28
Check Exhaust Tube Pressure
Exhaust Pressure Switch Testing and Replacement
Exhaust Tube
pressure tap location
Exhaust tube
at bottom of heater
N
Replace
blocked vent switch.
(see page 29)
Is exhaust venting
system blocked or
obstructed? Also
check condensate
elbow and drain.
Clear obstruction.
Determine cause
and correct.
Y
Is vent system total
length compliant with
vent tables in the
instruction manual?
Reconfigure vent
system to be
compliant with
vent tables (see
“Specifications”).
Y
N
With monometer, take a
reading at the
exhaust
tube pressure tap location.
Is value negative (-) or
slightly postitive
(see illustration below).
Y
N
With ohmmeter check
pressure switch for
continuity. Contacts should
be closed.
Y
N
Pressure switch O.K.
28
Is pressure in exhaust tube near 2.7" w.c. or more? If so, correct
blockage (above). If exhaust pressure is low (0.40" or less), replace
pressure switch.