Exhaust pressure switch testing and replacement, Safety circuit trace, Warning – LAARS U.H.E. - Service Manual User Manual

Page 27

Advertising
background image

U.H.E Service Manual

Page 27

Reset button

Does blower

energize?

N

Sequence of operation:

The blocked vent pressure switch monitors the pressure in the exhaust tube. The switch contacts are normally closed and will

not open unless there is a blockage in the exhaust venting or terminal (snow, ice, debris). If the blocked vent pressure switch

contacts open after the thermostat initiates the blower, the blower will remain on for to 5 minutes waiting for the contacts to close.

If the contacts remain open, the blower will stop and the PURGE LED will flash for hot surface ignition models.

Check PURGE LED status.

Y

Refer to

“Check Collector Pressure”

(see next page)

Check blower for proper

operation (see page 25)

Is blower OK?

N

On within 5 minutes?

Pressure switch is OK.

Y

Y

Safety Circuit Trace

LED Status

Only power LED is on, or

Purge LED flashing.

Exhaust Pressure Switch Testing and Replacement

N

WARNING

120 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

Flashing after 5 minutes?

Error code 29 again?

Call for technical

support.

Correct blower problem

(see page 25)

N

Y

Note: HOT SURFACE IGNITION MODELS

ONLY - The blocked vent pressure switch

must be used with the revised ignition control,

identified with a yellow label.

Heater side

harness

Control side

harness

27

Y

Is there continuity

Through GREY

wire leads of heater side

safety circuit harness?

(see photo below)

N

Y

Is there continuity

through RED

wire leads of heater side

safety circuit harness?

(see photo below)

N

Safety Circuit OK,

(see page 36)

Replace exhaust

pressure switch (see

page 29)

Replace vent safety

switch.

(see page 37)

Call technical

support.

Y

N

Depress reset

button on vent

safety switch. Is

there continuity

across high limit

switch?

(see photo below)

Check PURGE LED status

on ignition module,

Flashing after 45 seconds?

Does heater

function?

Verify proper

switch operation.

(see page 36)

N

Y

Y

WARNING

Make sure exhaust collector compartment is not

overheating (350°F) before resetting vent safety

switch. If there is evidence the collector compartment

is overheating, CALL TECHNICAL SUPPORT.