Laars Sequencing Controls

SET POINT CONTROL WITH OSS SEQUENCING

Dip Switch 8 - OFF

Press SELECT

Button

DISPLAY

Press and hold either the UP or DOWN button to adjust

Once

Set Point

The Set Point is the temperature which the SC will sequence stages to hold. Note that if you are

using the External Set Point, you will not be able to change the Set Point unless you adjust the 4-

20mA input. The Set Point is adjustable between -30°F to 250°F. Default is 70°F.

Twice♦

Outdoor Temp

This is the outdoor sensor temperature value.

3 Times♦♦

Outdoor Cutoff

Available only when the outdoor sensor is installed. When the outdoor temperature falls below the

Outdoor Cutoff value, the SC will activate stages for heat. The Outdoor Cutoff can be set ON or OFF

and from 40 to 100°F. Default is 60°F.

3 or 4 Time

System Delay

The System Delay controls how long the System relay will remain energized after the last Output has

been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable

from 0 to 30 minutes. Default is 0.

4 or 5 Times♦♦

Program Offset

The Programmed Offset fi ne tunes the Pressure input or the External Set Point. With a known 4mA

input, the offset can be set to make the External Set Point 110°F. The Program Offset is adjustable

between -10°F to +10°F. Default is 0°F.

4 or more Times

Throttling Range

The throttling range sets the number of degrees or psi above and below the Set Point where stages

will be turned on or off. The Throttle Range is adjustable from 1°F to 20°F. Default is 5°F. See page

24 for details.

5 or more Times♦♦

Setback

The Setback adjusts the number of degrees the Set Point water temperature will be reduced when

Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a

closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.

5 or more Times♦♦

DHW Priority Time

Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is

OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW

call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will

energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.

Default is 0.

5 or more Times♦

Default

The SC returns to the default display of system water temperature.

♦ Actual temperature values are not adjustable

♦♦ May not be available, depending on status of the outdoor sensor and dip switches.