SC-6P OUTPUT WIRING

INSTALLING THE OUTPUT RELAYS

• Each OUTPUT which is to be used must have a relay installed in the socket.

OUTPUT

OUTPUT

• Each Boiler has an individual Pump associated with it.

• The SC-6P also has a SYSTEM relay which can be used for main or system pumps, or

SYSTEM

SYSTEM

any other application where an output is needed when any stage has been activated.

• Check the charts on the pg. 17 to locate where the relays should be installed for each

particular type of installation.

• To install a relay, orient the pins and then press it gently into the appropriate socket.

• Any OUTPUT which does not have a relay must have its stage switch to the OFF

OUTPUT

OUTPUT

position (see pg. 23).

WIRING THE STAGE OUTPUTS

• Each output has one Normally Open (N.O.) relay contact

• The N.O. contacts are dry contacts only. They do not source any voltage.

• Each N.O. contact is capable of switching 6A resistive.

• Total output of all relays, including the SYSTEM must not exceed 15A.

SYSTEM

SYSTEM

ON/OFF Units

• Each unit has one Pump relay and one Stage relay associated with it.

• Connect the N.O. pump relay contacts in series with the unit’s pump starter.

• Connect the N.O. boiler relay contacts in series with the unit’s limit circuit.

2 Stage (Lo/Hi) Units

• Each unit has one Pump relay and two Stage relays associated with it.

• Check the chart for the Pump, Lo and Hi OUTPUT positions.

OUTPUT

OUTPUT

• Connect the N.O. pump relay contacts in series with the unit’s pump starter.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.

3 Stage (Lo/Mid/Hi) Units

• Each unit has one pump relay and three stage relays associated with it.

• Check the chart for the Pump, Lo, Mid and Hi OUTPUT positions.

OUTPUT

OUTPUT

• Connect the N.O. pump relay contacts in series with the unit’s pump starter.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the Mid N.O. relay contacts to the Mid control circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.

4 Stage (Lo/Mid/Hi) Units

• The unit has one pump relay and four stage relays associated with it.

• Check the chart for the Pump, Lo, LoMid, HiMid and Hi OUTPUT positions.

OUTPUT

OUTPUT

• Connect the N.O. pump relay contacts in series with the unit’s pump starter.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the LoMid N.O. relay contacts to the LoMid control circuit.

• Connect the HiMid N.O. relay contacts to the HiMid control circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.

SC

Outputs

ON/OFF Units

2 Stage Units

3 Stage Units

4 Stage Units

NO

C

To Pump

Starter

NO

C

Limit

Circuit

Boiler Pump

Output

Boiler

Output

NO

C

To Pump

Starter

Boiler Pump

Output

NO

C

Limit

Circuit

Lo

Output

NO

C

Hi

Circuit

Hi

Output

NO

C

To Pump

Starter

Boiler Pump

Output

NO

C

Limit

Circuit

Lo

Output

NO

C

Mid

Circuit

Mid

Output

NO

C

Hi

Circuit

Hi

Output

NO

C

To Pump

Starter

Boiler Pump

Output

NO

C

Limit

Circuit

Lo

Output

NO

C

LoMid

Circuit

LoMid

Output

NO

C

HiMid

Circuit

HiMid

Output

NO

C

Hi

Circuit

Hi

Output

WARNING

This Laars Heating Systems control is strictly an operating control; it should

never be used as a primary limit or safety control. All equipment must have its

own certifi ed limit and safety controls required by local codes. The installer must

verify proper operation and correct any safety problems prior to the installation of

this Laars Heating Systems control.

Additional output relays can be

ordered separately (CA002300). Each

active Stage Output must have a relay.