LAARS Heating Systems

OUTDOOR RESET WITH NORMAL SEQUENCING

Dip Switch 6 and 7 - OFF and 8 - ON

Press SELECT

Button

DISPLAY

Press and hold either the UP or DOWN button to adjust

Once♦

Calculated

This is the water temperature the SC will stage outputs to hold. It is based on outdoor temperature,
Reset Ratio, and the Offset value. If OFF is shown, there is no call for heat. If

PrF

is shown, the SC

is waiting for a Prove signal before activating stages.

Twice♦

Outdoor Temp

This is the outdoor sensor temperature value.

3 Times

Outdoor Cutoff

When the outdoor temperature falls below the Outdoor Cutoff value, the SC will give heat. When the

outdoor temperature is above the Outdoor Cutoff, the Calculated value will be OFF and no stages will

be activated except on a DHW call. The Outdoor Cutoff can be set ON or OFF and from 40 to 100°F.

Default is 60°F.

4 Times

Reset Ratio

The Reset Ratio controls the amount of heat which enters the heating system based on the outdoor

temperature. A higher numbered Reset Ratio will result in a higher Calculated water temperature.

See the chart on pg. 19 for the reset curves. The Reset Ratio is adjustable from 1 to 12. Default is 7.

5 Times

Offset

The Offset moves the reset curves vertically up or down. For example, changing the offset from 0 to

-10 will decrease the water temperature 10°F regardless of outdoor temperature or the reset curve

selected. The Offset is adjustable from -40°F to 40°F. Default is 0°F.

6 Times

Reaction Time

The Reaction Time controls the minimum run time for a stage (1/2 the Reaction Time). Also, it con-

trols how long should a stage run before it activates/subtracts another stage. It is adjustable from half

a minute (0.5) to 8.0 minutes. Default is 2 minutes.

7 Times

System Delay

The System Delay controls how long the System relay will remain energized after the last Output has

been turned off or the outdoor temperature rises above the Starter. The System Delay is adjustable

from 0 to 30 minutes.

8 Times

Purge Time

The Purge Time should be set to the length of the unit’s purge cycle. The Purge Time will apply

when any ON/OFF unit is activated. On multiple stage units, the Purge Time will only apply to the Lo

stages. The Purge Time is adjustable from 0.0 to 10.0 minutes. Default is 0.

9 Times

Boiler runtime

This is the minimum amount of time any boiler will run after the Purge cycle has been completed. This
timer does not apply when only one stage is running, the Last Stage Hold

LSH

applies in that case.

The Boiler Runtime is adjustable between 0 to 60 minutes. Default is 0.

10 Times

Last Stage Hold

To prevent short cycling of the last stage in low load conditions, the system temperature can exceed

the Calculated water Temperature by the amount selected by the Last Stage Hold before the last

stage is turned off. The Last Stage Hold is adjustable between 0°F to 20°F. Default is 10°F.

11 Times

Setback

The Setback adjusts the number of degrees the Set Point water temperature will be reduced when

Input terminals 7 and 8 are closed. If the Setback is set to 0, then the system will Shutdown on a

closure. The Setback is adjustable from 0°F to 40°F. Default is 0°F.

12 Times♦♦

DHW Priority Time

Only available when the System Output is set to System Pump (dip switch 1 is ON and dip switch 6 is

OFF ) This setting adjusts the amount of time the System relay output will remain off during a DHW

call. If the DHW call is not satisfi ed before the DHW priority time has elapsed, the System relay will

energize to provide heat. The DHW Priority is adjustable from 0 to 4 hours in half hour increments.

Default is 0.

12 to 13 Times♦

Default

The SC returns to the default display of system water temperature.

♦ Actual temperature values are not adjustable

♦♦ May not be available, depending on status of the outdoor sensor and dip switches.