Laars Sequencing Controls

WIRING THE STAGE OUTPUTS

• For SC-6 and SC-12 see pg. 14.

• For SC-6P see pg. 15.

WIRING THE SYSTEM OUTPUT

Combustion Air Damper

• To select the Combustion Air Damper mode of operation, Dip Switch 1 must be OFF.

• Wire the Air Damper to System relay terminals marked C and N.O.

• The Combustion Air Damper option causes the System relay to act as follows:

- If there is no call for stage output, the System relay is off

- On a call for stage output, the System relay is energized

- When the PROVE input is made, the lead stage is energized

PROVE

PROVE

- The System relay remains energized as long as any stage is active

- When the last stage turns off, the System relay remains energized for the period of

time set by the System Delay (see pg. 22)

- Then the System relay is turned off.

• To give the damper time to open, wire the damper motor end switch into the PROVE inputs. The

PROVE

PROVE

PROVE input can be used in a

PROVE

PROVE

similar fashion to provide a delay for any equipment being energized by the System relay.

• The Combustion Air Damper operation can also be used to activate any piece of equipment that should be on whenever any stage

is active or can provide a signal to other equipment that one or more stages of the SC has been activated.

• The System Relay is a SPDT output capable of switching 6A resistive.

• Check the wiring information provided by the damper motor or other equipment manufacturer for the appropriate method to

activate the equipment with a SPDT output.

System Pump

• To select the System Pump mode of operation, Dip Switch 1 must be ON.

ON

ON

• Wire the System Pump to System relay terminals marked C and N.O.

• When there is no call for DHW, the System relay will be energized whenever the

Outdoor temperature is below the Outdoor Cutoff COF and the Shutdown is not

active. The System relay will remain energized even if all Output Stages are off.

• If an outdoor sensor is not connected or registers a fault condition:

- The System relay will be energized when any stage is active

- After the last stage is turned off, the System relay will remain energized for the period of time set by the System Delay (see pg.

22) and then turn off.

• When the control is set for “no DHW priority” (see pgs. 8 and 9) and there is a call for DHW:

- When the outdoor temperature below the Outdoor Cutoff + 2°F (COF + 2°F), the System relay output will be active.

- Otherwise, the System relay will be off above COF + 2°F (after the System Delay Sd has expired).• When the control is set

for “DHW priority” (see pgs. 8 and 9):

• When the control is set for “DHW priority” (see pgs. 8 and 9):

- The System relay will be off for an adjustable period of time set by the DHW Priority Time dhP.

- After the Priority Time has elapsed, when the outdoor temperature is below the Outdoor Cutoff + 2°F (COF+ 2°F) setting, the

System relay will be energized.

- When the outdoor temperature is 2°F above the Outdoor Cutoff ( COF +

2°F), the System relay will be off at all times.

• The system output is capable of switching 6A resistive.

BEFORE POWER UP

• The dip switches must be set correctly for the application. Check the dip

switch chart on pg. 4 to make sure the SC is set properly before power up.

• Each Stage Output which is to be active (and has a relay installed) should have its OFF/AUTO/ON switch in the

OFF/AUTO/ON

OFF/AUTO/ON

AUTO position.

• Any Stage Output which is not to be active (or any output without a relay) should have its OFF/AUTO/ON switch in the

OFF/AUTO/ON

OFF/AUTO/ON

OFF

position.

• Set the LEAD STAGE switch in the

LEAD STAGE

LEAD STAGE

AUTO position for automatic rotation.

SYSTEM

C.

N.C.

N.O.

Combustion

Air Damper

Li

ne

N

eu

t

SYSTEM

C.

N.C.

N.O.

System Pump

Li

ne

N

eu

t

WARNING

WARNING

The SC is NOT a safety

control. Make sure damper

is wired back into boiler for

safety.

NOTICE

The SC DOES NOT source

power. A separate power

source must be supplied for

equipment being controlled.